Page 20
OPERATION
MANUAL OPERATION
Powerful springs. Do not
place your hands or any
part of your body inside
the circuit breaker while
the indicators show
CHARGED (yellow) or ON
(red).
To avoid damaging the
mechanism, do not close
the circuit breaker when
the On-Off Indicator shows
ON (red).
MANUAL CLOSING (Motor-Operated MU and
ML Types):
1. Check to make sure that the On-Off
indicator shows OFF (green).
2. Attach the charging handle to the breaker if it
is not already attached.
3. If the closing spring status indicator shows
DISCHARGED (white):
Turn the charging handle clockwise 3 to 5
times to charge the closing spring (Fig. 23).
(Closing Spring Status Indicator changes to
CHARGED, Yellow) When the handle is
released, it returns to its normal position, and
do not attempt to turn again.
If the closing spring status indicator shows
CHARGED (yellow):
Do not attempt to turn handle.
Pushing the Green lever (Fig. 24) in the
direction of the arrow closes the circuit
breaker (On-Off indicator changes to ON)
Fig. 23 Preparing to Manually Charge
Breaker
Fig. 24 Manually Closing Breaker
WARNING
CAUTION
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com