25
ICC
unit is highlighted, or just directly enter the target unit’s IP address into the
address (URL) field of your web browser. Refer to Figure 7 for a representative
screenshot of the web server interface.
In order to access the web server and view the parameter values, destination
TCP ports 80 and 2000 must be accessible from the client computer. If an
“XML socket connection failed” error message is displayed in the information
window, and no parameter values are shown, this is typically indicative of port
2000 being blocked by a firewall or Ethernet router situated between the client
computer and the interface card.
10.2
Authentication
For security, the interface requires valid user authentication whenever the web
page is accessed. The authentication request will appear as a browser popup
box that will request entry of a user name and password. Refer to Figure 8.
Figure 8: Web Server Authentication
The factory-default user name is “root”, and the password is “icc”. Note that the
username and password are case-sensitive, and that once authenticated, the
authentication will remain in effect from that point until all browser windows are
closed. The authentication credentials can also be changed from their default
settings (refer to section 10.7.3.)