8.4 Fixed Value Output
(Loop Check)
The fixed value output is the function to output a fixed current and/or a fixed pulse output
independently of the flow rate signal.
The following parameters can be set here:
(1) Fixed value output On/Off setting
(2) Fixed current output value
(3) Fixed pulse output value
Notes
•
Fixed pulse output can be sent out only when DO1 or DO2 is set for pulse output.
•
When the mode is switched to the fixed output mode by DI function, the preset values of items (2)
and (3) above will be output.
•
In the fixed output mode, the condition of DO output (other than pulse output) will be
maintained.
Fixed value output On/Off setting
Fixed output mode can be selected by the setting as follows.
Selection Mode
1: ON
Fixed value output mode On
Current output and pulse output become fixed output values.
2: OFF
Fixed value output mode Off
Fixed output mode will be turned off and the mode goes to the
normal measurement mode.
When the fixed value output is set to ON, the main indicating unit only is displayed and the current
output set value is displayed in the lower line in the measurement mode.
Display example:
1.000 m/s
* FIX.OUT 20.0 mA
Flow velocity is displayed in main
indicating unit
Fixed current value is displayed
Note: When power is turned off and on again, the fixed output On/Off setting will be turned off.
Fixed current output value
The current value used in the fixed output mode is set.
Fixed current output value can be set in the range of 3 to 24mA in increments of 0.1mA.