6F8A0917
- 88 -
Changing the output low limit value setting.
The following is an example to change the output low limit setting from 4.0mA (1: 4.0mA) to
3.2mA (2: 3.2mA).
Switch operation
Display example
Description
D5: LOW LIMIT
1:4.0mA
Select D5: LOW LIMIT from the setting item selection menu.
The currently set output low limit value appears.
D5: LOW LIMIT
1:4.0mA
The cursor appears.
D5: LOW LIMIT
2:3.2mA
Press
to select 2:3.2mA.
D5: LOW LIMIT
2:3.2mA
The display blinks and the set value is displayed for
confirmation.
Press
MENU/ENT
again to write the data. Then the cursor
disappears and the display returns to the condition that the
setting value is displayed.
D5: LOW LIMIT
Returns to the menu of setting item selection.