– 23 –

Lite-Vision plus Remote Controller

Installation Manual

Entering the model name and serial number

Enter the model name and serial number manually for a Light commercial outdoor unit. Information data is loaded 
automatically for Light commercial indoor units, VRF indoor units (excluding large capacity air discharge type and 
duct type), and VRF outdoor units. Enter the model name and serial number manually after replacing the circuit 
board to the service circuit board (unless entering information manually before replacement of the circuit board).

<Flow chart of usual process>

Entering the model name and serial number manually

Product

Model name and serial number display

Light commercial indoor unit

Information data is loaded automatically from the indoor unit and displayed.

VRF indoor unit

Information data is loaded automatically from the indoor unit and displayed.
Enter information manually for the indoor unit of large capacity air discharge 

type and duct type.

VRF outdoor unit

Information data is loaded automatically from the outdoor unit and displayed.

Light commercial outdoor unit

Enter information manually on the remote controller.

Service circuit board

Enter information manually on the remote controller.

1

Push the [

 

 ] / [

 

 ] button to select 

“2. Outdoor model name” on the “Register 
service info” screen, then push the 

 

Set”  [

 

F2] button.

Æ

Select “3. Outdoor unit serial No.” to enter the 
serial number of the outdoor unit.

Æ

Select “4. Indoor model name” to enter the 
model name of the indoor unit.

Æ

Select “5. Indoor unit serial No.” to enter the 
serial number of the indoor unit.

Does the indoor unit / outdoor unit automatically load information data of model 

name and serial number to the remote controller?

The model name and serial number loaded from the unit 

are displayed.

1. Manual entry is not needed.

2. Select “Indoor unit (Outdoor unit)” for the display mode 

(factory default).

1. Enter the model name and serial number of the unit 

manually on the remote controller.

2. Select “Remote controller” for the display mode.

Yes

No

1.Service contact tel No.

2.Outdoor model name

 

3.Outdoor unit serial No.
4.Indoor model name 
5.Indoor unit serial No.

Register service info

Return

Set

Set

+00EH97062301.book  Page 23  Thursday, March 17, 2011  10:51 AM

Summary of Contents for Lite-Vision plus RBC-AMS51E-EN

Page 1: ...o Installation Manual 1 English Lite Vision plus Remote Controller Model name RBC AMS51E EN Read this manual before using the RBC AMS51E EN remote controller Refer to the Installation Manual supplied with the indoor unit for any installation instructions other than operations of the remote controller Installation Manual 01EN00COV fm Page 1 Thursday March 17 2011 1 11 PM ...

Page 2: ...up control 7 Requirements for installing two remote controllers 7 For first use 9 Note 9 Part Names and Functions 10 Monitor screen 11 Initial setting 12 1 Clock 12 2 Name of room 13 3 Screen contrast 14 4 Backlight 15 5 Key lock 15 6 Header follower 16 7 Language 17 8 Press hold 4sec 18 Field setting menu 19 1 Test Mode 19 2 Register service info 21 3 Alarm history 25 4 Monitor function 26 5 DN s...

Page 3: ... require hospitalization or long term treatment as an outpatient 3 Damage to property indicates damage extending to buildings household effects domestic livestock and pets Symbols Meaning of Symbols Indicates prohibited items The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol Indicates compulsory mandatory items The actual contents...

Page 4: ...ation Manual Accessory Parts No Part name Quantity 1 Remote controller 1 2 Screws small M4 x 20 2 3 Wood screws M3 8 x 16 2 4 Owner s Manual 1 5 Installation Manual This manual 1 6 CD ROM 1 00EH97062301 book Page 3 Thursday March 17 2011 10 51 AM ...

Page 5: ... a place exposed to direct sunlight or direct outside air such as the side of a window Do not install the remote controller in a place behind something or to the rear side of an object where air flow is not sufficient Do not install the remote controller in a freezing box or refrigerator as the remote controller is not waterproof Install the remote controller vertically to the wall Installation di...

Page 6: ...pe VCTF 0 5 mm2 to 2 0 mm2 x 2 Total length of remote control wiring and inter wiring between remote controllers L L1 L2 Ln 1 remote controller 2 remote controllers 2 remote controllers including a wireless remote controller Up to 500 m Up to 300 m Up to 400 m Total length of inter wiring between remote controllers L1 L2 Ln Up to 200 m Indoor unit Indoor unit Indoor unit Indoor unit Remote control...

Page 7: ... pieces supplied with the remote controller to attach the rear case of the remote controller to the wall Do not use an electrical screwdriver Do not over tighten the screw Tightening torque is up to 2 kg f cm otherwise the rear case may be damaged 3 Connect the electrical wire from the indoor unit to the terminal block of remote controller Refer to Wire the remote controller Check the terminal num...

Page 8: ...troller system one or more units are operated from two remote controllers Up to two remote controllers can be installed Set the follower remote controller Set from 6 Header follower in 10 Initial setting on the MENU screen For details refer to the page 16 Install the remote controllers For the dual remote controller system install the remote controllers as follows 1 Set one remote controller as th...

Page 9: ... header Remote controller follower Sold separately Terminal block for the remote control wiring Earth Indoor unit Remote control wiring Locally procured 0 5 mm2 to 1 25 mm2 Remotecontroller header Remote controller follower Sold separately Terminal block for the remote control wiring Earth Indoor unit Remote controller inter unit wires for group control Locally procured Remotecontroller header Rem...

Page 10: ...tes before the remote controller becomes operable When the power is turned on from the second time It takes about 1 minute before the remote controller becomes operable Note For the operation of switching the room temperature sensor or the settings of the test operation refer to the page 19 Power on flashes disappears Remote controller becomes operable About 5 minutes Power on flashes disappears R...

Page 11: ...screen selects a menu item 3 button During normal operation adjusts the temperature On the menu screen selects a menu item 4 MENU button Displays the menu screen 5 F1 button Varies its function according to the setting screen 6 F2 button Varies its function according to the setting screen 7 CANCEL button Functions as indicated on the screen such as returning to the previous menu screen 8 MONITOR b...

Page 12: ... The monitor screen appears 2 Push CANCEL button to return 1 Displays the set temperature 2 Displays the temperature measured by the indoor temperature sensor of the indoor unit If the sensor is set to that of the remote controller the temperature measured by the remote controller sensor is displayed 3 Displays the temperature around the vent of the outdoor unit 4 Displays the remaining time until...

Page 13: ... Push the CANCEL button to return ÆThe screen returns to the menu screen 1 Push the button to select 1 Clock on the Initial setting screen then push the Set F2 button 2 Push the button to select the year month date and time ÆPush the F1 F2 button to set the value 3 Push the MENU button Initial setting 1 2 1 Clock 2 Name of room 3 Screen contrast 4 Backlight 5 Key lock Set Return Set Set Initial se...

Page 14: ...nge is from January 1st 2010 to December 31st 2099 1 Push the button to select 2 Name of room on the Initial setting screen then push the Set F2 button 2 Set the name of the remote controller Enter the characters of the name in the screen 1 Move the cursor to select the character with the button and F1 F2 button the selected character is highlighted then push the MENU button Name of the remote con...

Page 15: ...en then push the Set F2 button 2 Push the F1 F2 button to adjust 3 Push the MENU button ÆThe screen returns to the Initial setting screen Return Set Fix ABCDE FGH I J KLMNO PQRST U W X Y Z abcde f g h i j klmno p q r s t uvwxy z 12345 67890 Bedroo Del Return Set Del ABCDE FGH I J KLMNO PQRST U W X Y Z abcde f g h i j klmno p q r s t uvwxy z 12345 67890 705A Fix Initial setting 1 2 1 Clock 2 Name o...

Page 16: ...sh the Set F2 button 2 Push the button to select a key to lock unlock 3 Push the z F1 button to select Lock or z F2 button to select Unlock 4 Push the MENU button ÆWhen Lock is selected the key cannot be used during key lock When Unlock is selected the key can be used even during key lock ÆAll keys are unlocked while Check is displayed ÆFor the key lock setting refer to the owner s manual ÆThe fac...

Page 17: ...ote controller is set as the Follower remote controller Schedule timer Off reminder timer Night operation Save operation Return back NOTE Some functions are not available when the remote controller is set as the Follower remote controller In the dual remote controller system the latter operation overrides the former The remote controller is set as Header remote controller as factory default 1 Push...

Page 18: ... button to select a language 3 Push the MENU button The screen text changes to the selected language ÆThe factory default is English These two screens appear for RBC AMS51E EN Initial setting 2 2 6 Header Follower 7 Language 8 Press hold 4 sec Set Return Set Language 1 2 English Italian Greek Russian Turkish Return Fix Language 2 2 Polish Return Fix Polski 00EH97062301 book Page 17 Thursday March ...

Page 19: ...ush the button to select ON or OFF 3 Push the MENU button ÆWhen ON is selected the air conditioner starts stops running when the ON OFF button is pressed and hold 4 seconds ÆWhen OFF is selected the air conditioner starts stops running when the ON OFF button is pressed Initial setting 2 2 6 Header Follower 7 Language 8 Press hold 4 sec Set Return Press hold 4sec ON OFF Return Fix Set 00EH97062301 ...

Page 20: ...to prevent a continuous operation the forced test operation is released after 60 minutes have passed and returns to the normal operation CAUTION Do not perform the forced test mode for purposes other than the test mode because it applies an excessive load to the devices 1 Push the MENU button to display the menu screen 2 Push and hold the MENU button and the button at the same time to display the ...

Page 21: ...ted during the test mode ÆCheck codes are displayed as usual 3 When the test mode is finished push the button to select 1 Test Mode on the Field setting menu screen then push the Set F2 button The screen 3 appears ÆPushing the Yes F1 button stops the test mode screen and continues the normal operation NOTE The test mode stops after 60 minutes and the screen returns to the normal detailed display 1...

Page 22: ...lly Automatic loading is not available for some models In this case enter information manually Enter the contact number for service displayed in 2 Service information of 11 information on the menu screen Enter the model name and serial number displayed in 1 Model information of 11 information on the menu screen Push the MONITOR button Refer to 4 Monitor function page 26 for details When the group ...

Page 23: ...ame Enter reset the model name of the indoor unit 5 Indoor unit serial No Enter reset the serial number of the indoor unit 1 Push the button to select 1 Service contact tel No then push the Set F2 button 2 Move the cursor to select the character selected character is highlighted with the F1 F2 button then enter the contact number with the button 3 Push the MENU button 1 Service contact tel No 2 Ou...

Page 24: ... loaded automatically from the outdoor unit and displayed Light commercial outdoor unit Enter information manually on the remote controller Service circuit board Enter information manually on the remote controller 1 Push the button to select 2 Outdoor model name on the Register service info screen then push the Set F2 button ÆSelect 3 Outdoor unit serial No to enter the serial number of the outdoo...

Page 25: ...oor unit select 2 Serial No selection ÆTo select the model name of the indoor unit select 2 Model name selection ÆTo select the serial number of the indoor unit select 2 Serial No selection 2 Push the button to select Remote controller or Outdoor unit ÆWhen Outdoor unit or Indoor unit is selected the model name or serial number received from the outdoor or indoor unit is displayed ÆWhen Remote con...

Page 26: ...e date and time when the error occurred for the first time is displayed for the repeated alarm 1 Push the Reset F2 button while the list of alarm history is displayed 2 Push the Yes F1 button after the confirmation screen is displayed ÆDelete the alarm history in each remote controller when the dual remote controller system is used 1 Manual model name input 2 Model name selection Outdoor model nam...

Page 27: ...function on the Field setting menu screen then push the Set F2 button ÆPush the button to select the code to check data 2 Refer to the Installation Manual supplied with the indoor unit or outdoor unit or service manual for details about the check code and data 3 Push the CANCEL button to return to the Field setting menu screen Monitor function Code 00 Data 0024 Return Set 00EH97062301 book Page 26...

Page 28: ...th the button 2 Refer to the Installation Manual supplied with the indoor unit or service manual for details about the DN code and data 3 Push the MENU button to set the other DN codes After Continue is displayed on the screen push the Yes F1 button 4 Push the No F2 button to finish the setting operation appears on the screen for a while then the screen returns to the Field setting menu screen ÆPu...

Page 29: ... 28 Lite Vision plus Remote Controller Installation Manual EN 00EH97062301 book Page 28 Thursday March 17 2011 10 51 AM ...

Page 30: ...EH97062301 01ENCOV4 fm Page 27 Thursday March 17 2011 1 12 PM ...

Reviews: