2. Basic Permutations of Indoor to Outdoor Units
The indoor units are given a code number according to their capacity rank - see below
10
RAV1253/460/1/2/3
8
RAV1003/360/1/2/3
6
RAV713/260/1/2/3
5
RAV202/3
4
RAV453/160/1/2/3
3
RAV132/133
2
RAV103
Code Number
Model Number
Multiple indoor units may be connected to one outdoor unit, providing the total indoor code does not
exceed the outdoor unit code number. The outdoor unit codes are listed below
27
3
8
MAR-M101HTM8-E
21
3
8
MAR-M81HTM8-E
Max. Code
Min Code
Max.. No. Indoor Units
Model
When connecting up to four single indoor units only one multi controller is required, if more single
indoor units are needed then two multi controllers must be used. When connecting a twin indoor
arrangement to one multi controller branch the capacity code will be the sum of both indoor unit
codes.
Example :
24
Total
10
5
Twin
RAV202KH(W)
5
5
Single
RAV202KH(W)
6
3
Twin
RAV133TUH
3
3
Single
RAV133TUH
Total Capacity Code
Indoor Capacity Code
Arrangement
Model No.
The total capacity codes for the example above are within the maximum permitted for a 10hp
(MAR-F101HTM8-E) outdoor unit therefore the use of a twin arrangement is acceptable.
NOTE :
The maximum duty from the system cannot exceed the maximum capacity of the outdoor
unit, it is possible to use indoor uits with a total capacity of 135% of the outdoor unit capacity.