5. Schematic Refrigeration Diagram
Outdoor Unit
DRIER
STRAINER
LIQUID
TANK
EXPANSION
VALVE
CHECK VALVE
HEAT
EXCHANGER
ThE
PRESSURE
SENSOR
INVERTER
H.P. SWITCH
ThD1
INVERTER
COMPRESSOR
LOW
PRESSURE
SWITCH
ThS
D.O.L.
COMPRESSOR
ThD2
D.O.L.
H.P.SWITCH
ACCUMULATOR
PMV1
COOLING
BYPASS
4-WAY
VALVE
SV1
HIGH
PRESSURE
RELEASE
COMPRESSOR
SV4
FOR
COMP 2
START UP
SV2
FOR GAS
BALANCE
SERVICE
VALVE
SERVICE
VALVE
Specification of Outdoor Unit Components
74
(W)
Crankcase Heater (240vac)
Energised for Heating
Four Way Valve
32.8 @ 0ºC , 10 @ 25ºC , 3.6 @ 50ºC
(k
Ω)
ThS & ThE
50 @ 25ºC , 17.9 @ 50ºC , 3.35 @ 100ºC
(k
Ω)
ThD1 & ThD2 Sensor
Break on Drop : Trip 3.5 , Reset 20
P.S.I.G.
L.P. Switch
Make on Rise : Trip 425 , Reset 340
P.S.I.G.
H.P. Switch DOL
Break on Rise : Trip 425 , Reset 340
P.S.I.G.
H.P. Switch Inv.
Trip 115ºC
✁
5ºC
Thermal Cut-out
6
No. Poles
1.12 - 1.44
Current (A)
150
Consumption (W)
220 / 240 , single phase , 50Hz + Neutral
Power Supply
Single Phase Induction
Motor Type
STF-200-150C
Type Number
Fan Motor
Inv.1.49 / DOL 2.51
Coil Resistance (
Ω
)
7.5
5.6
Output (kW)
415/380 , 3-phase , 50Hz + Neutral
Power Supply
Three Phase Induction
Motor Type
HV1201CW-Y12
HV991CW-Y12
Type Number
Compressor
MAR-M101HTM8-E
MAR-M81HTM8-E
Model Number
TOSHIBA
AUGUST 1997
Page 11