127
Errors detected by TCC-LINK central control device
Location
of
detection
Description
System status
Check code detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Sub-code
–
5
0
C
TCC-LINK TCC-LINK
central control
device
transmission
trouble
Continued
operation
Central control device is
unable to transmit signal.
Check for trouble in central
control device.
Check for trouble in central
control communication
line.
Check termination
resistance setting.
–
6
0
C
TCC-LINK
central control
device reception
trouble
Continued
operation
Central control device is
unable to receive signal.
Check for trouble in central
control device.
Check for trouble in central
control communication
line.
Check termination
resistance setting.
Check power supply for
devices at other end of
central control
communication line.
Check trouble in P.C.
boards of devices at other
end of central control
communication line.
–
2
1
C
General-
purpose
device
I/F
Blanket alarm
for general-
purpose device
control interface
Continued
operation
Trouble signal is input to
control interface for general-
purpose devices.
Check check code input.
P30
Differs according to
nature of alarm-causing
trouble
TCC-LINK Group control
follower unit
trouble
Continued
operation
Trouble occurs in follower
unit under group control.
([P30] is displayed on central
control remote controller.)
Check check code of unit
that has generated alarm.
(L20 displayed.)
Duplicated
central control
address
Continued
operation
There is duplication in central
control addresses.
Check address settings.
Check code
117
A10-1510.indb 117
A10-1510.indb 117
2016/04/08 17:21:10
2016/04/08 17:21:10
AMP Air Conditioning