54
7-4. Demand response for Australia
Models for Australia are appliances for DRED (Demand Response Enabling Device) that complies with
AS/NZS 4755.3.1.
These models support only DRM1.
AS/NZS 4755
DRM1
DRM2
DRM3
Demand response mode
Description
DRM1
Compressor off
DRM2
Not available
DRM3
Not available
DRED installation position
Demand P.C. board
DRM1
DRM2
DRM3
COM
Connect the wiring to the
demand P.C. board as shown in
(This model is valid only for
demand response mode DRM1.)
Wires for
indoor/outdoor
communication
Outline of DRED wiring
CN101
CN106
CN102
CN100
COM DRM1 DRM2 DRM3
L
Trans-
former
DRED
Locally procured
Power supply
MCC-1653
DEMAND
P.C. BOARD
MCC-1551
NOISE FILTER
P.C. BOARD
U1
To central
controller
To indoor
unit
N
U2 U3 U4
MCC-1639
I/F P.C. BOARD
{
{
For details of the wiring, refer to the
wiring diagram which is adhered to the
front panel.
46
A10-1510.indb 46
A10-1510.indb 46
2016/04/08 17:20:52
2016/04/08 17:20:52
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk