74
Manual address setting with the remote controller
Procedure when setting indoor units’ addresses first under the condition that indoor wiring has been completed and
outdoor wiring has not been started (manual setting using the remote controller)
Wiring example of 2 refrigerant lines
In the example above, disconnect the remote controller connections between the indoor units and connect
a wired remote controller to the target unit directly before address setting.
Pair the indoor unit to set and the remote controller one-to-one.
Turn on the power.
1
Push and hold the
,
, and
buttons at the same time for more than 4 seconds.
LCD starts flashing.
Line (system) address
1
1
1
2
2
Indoor unit address
1
2
3
1
2
Group address
1
Header unit
2
Follower unit
2
Follower unit
2
Follower unit
2
Follower unit
Outdoor
unit
Outdoor
unit
Remote
controller
Indoor unit 1
Indoor unit 2
Indoor unit 3
Indoor unit 1
Indoor unit 2
Refrigerant line 1
Refrigerant line 2
SET DATA
CODE No.
60
A10-1510.indb 60
A10-1510.indb 60
2016/04/08 17:20:55
2016/04/08 17:20:55