101
8-7-4. Remote controller distinction function
This function is provided to distinguish the remote controller connected to the indoor unit from the outdoor unit for
a refrigerant circuit system by using switches on the interface P.C. board of the outdoor unit.
<Distinction procedure>
Power ON
Be sure to turn on the power of the indoor unit
prior to the power of the outdoor unit.
7-segment display
Set the display select switches on the
interface P.C. board of the outdoor unit
as follows:
Set SW01 / SW02 / SW03 to [2/4/1]
Press the push-switch SW04 on the same
board for 2 seconds or more.
7-segment display
"Checking" display of the connected
remote controller flashes.
Press the push-switch SW05 on the
interface P.C. board of the outdoor
unit for 2 seconds or more.
Operation
Check the connected remote controller
End
Other end conditions:
1. 10 minutes have passed
2. SW01, SW02, or SW03 changed to other position.
SW09
SW07
SW11
SW06
SW10
SW12 SW13
SW16
SW14
SW17
D600 D601 D602 D603 D604
SW04
SW05
SW15
SW01
SW02
SW03
SW30
D600 D601 D602 D603 D604
SW04
SW05
SW15
SW01
SW02
SW03
Interface P.C. board
Push switch
7-segment
display [A]
Push switch
7-segment
display [B]
Rotary switches
87
A10-1510.indb 87
A10-1510.indb 87
2016/04/08 17:21:02
2016/04/08 17:21:02