Installation Manual
– 8 –
EN
2
Accessory Parts
NOTE
• Before installing the unit, check that the unit has the correct model name to prevent the wrong unit from being
installed in the wrong place.
• Before proceeding to braze the refrigerant pipe, be sure to pass nitrogen through the pipe.
• Before installing the indoor units, read the instructions in the installation manual provided with the indoor units.
• Before installing a branch pipe, read the instructions in the installation manual provided with the branch pipe kit.
Part name
Q’ty
Shape
Usage
Owner’s Manual
1
Hand this directly to the customer.
Installation Manual
1
Hand this directly to the customer.
CD-ROM
(Owner’s manual,
Installation manual)
1
-
For other languages that do not appear in this Installation
Manual, Please refer to the enclosed CD-ROM.
F-GAS label
1
Fill the items on the label after adding refrigerant.
Attached pipe
1
Gas pipe connection pipe
Ø19.05 to Ø22.22 (MCY-MHP1006HS8* only)
3
Installation of New Refrigerant Air
Conditioner
This air conditioner adopts the new HFC refrigerant (R410A) which does not deplete the ozone layer.
• R410A refrigerant is vulnerable to impurities such as water, oxidizing membranes, or oils because the pressure of
R410A refrigerant is higher than that of the former refrigerant by approximately 1.6 times.
As well as the adoption of the new refrigerant, the refrigerating oil has been also changed. Therefore, pay attention
so that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle of the new refrigerant
air conditioner during installation.
• To prevent mixing of refrigerant or refrigerating oil, the size of the charge port of the main unit or connecting section
of the installation tool differs to that of an air conditioner for the former refrigerant.
Accordingly, exclusive tools are required for the new refrigerant (R410A) as shown below.
• For connecting pipes, use new and clean piping materials so that water or dust does not enter.
Required tools and cautions on handling
It is necessary to prepare the tools and parts for installation as described below. The tools and parts which will be
newly prepared in the following items should be restricted to exclusive use.
Explanation of symbols
: Newly prepared (It is necessary to use it exclusively with R410A, separately from those for R22 or R407C.)
: Former tool is available.
Used tools
Usage
Proper use of tools / parts
Gauge manifold
Vacuuming, charging refrigerant
and operation check
Exclusive to R410A
Charging hose
Exclusive to R410A
Charging cylinder
Charging refrigerant
Unusable (Use the Refrigerant charging
balance.)
Gas leak detector
Checking gas leak
Exclusive to R410A
Vacuum pump
Vacuum drying
Usable if a counter-flow preventive adapter is
attached
Vacuum pump with counterflow Vacuum drying
R22 (Existing article)
Flare tool
Flare processing of pipes
Usable by adjusting size
Bender
Bending processing of pipes
R22 (Existing article)
Refrigerant recovery device
Recovering refrigerant
Exclusive to R410A
Torque wrench
Tightening flare nut
Exclusive to Ø12.70 mm and Ø15.88 mm
Pipe cutter
Cutting pipes
R22 (Existing article)
Refrigerant canister
Charging refrigerant
Exclusive to R410A
Enter the refrigerate name for identification
Welding machine / Nitrogen gas
cylinder
Welding of pipes
R22 (Existing article)
Refrigerant charging balance
Charging refrigerant
R22 (Existing article)
EN-15
EN-16