101
(2)Outdoor unit data display (Displayed on each outdoor unit)
SW01 SW02 SW03
Description
1
1
1
Error data
A Displays outdoor unit No.: [U1] to [U4]
B Displays the check code (Only the latest one).
Displays [– – –] when there is no check code.
If there is an auxiliary code, the check code [
] appears for 3 seconds and
the auxiliary code [–
] for 1 second, alternately.
<SW04> Push function: Fan runs only for the unit with error. 7-segment A: [E.1]
<SW04 + SW05> Push function: Fan runs only for the unit without error. 7-segment A: [E.0]
<SW05> Push function: Fan operation interrupted.
2
–
A –
B –
3
Operation mode
A Stop: [… …]
Normal cooling: […C], Normal heating: […H], Normal defrosting: […J]
B –
4
Horse power of outdoor unit
A 8 Horse power: […8], 10 Horse power: [10], 12 Horse power: [12],
14 Horse power: [14], 16 Horse power: [16]
B […HP]
5
Compressor operation order
* Data of each compressor appears every 2 seconds in order.
If Compressor 3 does not exist, [– –.– – –] appears.
Normally: Displays the rotation count of compressor in decimal
7-segment display (A / B): [C1.
]
[C2.
]
[C3.
.
]
…
<SW04> Push SW function: Changes to the operation current value display (decimal)
7-segment display (A / B): [i1.
.
]
[i2.
.
]
[i3.
.
]
…
(Returns to normal display by <SW05> push)
6
Outdoor fan mode
A [FP]
B Mode 0 to 63: […0] to [63]
7
Compressor / Backup
A [C.b.]
B Displays the compressor backup setting status
Normally: [… … …]
Compressor 1 backed up: [1 … …]
Compressor 2 backed up: [… 1 …]
Compressor 3 backed up: [… … 1]
8
–
A –
B –
9
Control valve output data
Displays the electric valve control output status
A
B
4-way valve: ON / 4-way valve 2: OFF
H. 1
… … …
4-way valve: OFF / 4-way valve 2: ON
H. 0
… … …
10
SV2: ON / SV5: OFF / SV6: OFF
2. …
1 0 0
SV2: OFF / SV5: ON / SV6: ON
2. …
0 1 0
SV2: OFF / SV5: OFF / SV6: ON
2. …
0 0 1
11
SV3A: ON / SV3B: OFF / SV3C: OFF / SV3D: OFF
3. 1
0 0 0
SV3A: OFF / SV3B: ON / SV3C: OFF / SV3D: OFF
3. 0
1 0 0
SV3A: OFF / SV3B: OFF / SV3C: ON / SV3D: OFF
3. 0
0 1 0
SV3A: OFF / SV3B: OFF / SV3C: OFF / SV3D: ON
3. 0
0 0 1
12
SV41: ON / SV42: OFF / SV43: OFF
4. …
1 0 0
SV41: OFF / SV42: ON / SV43: OFF
4. …
0 1 0
SV41: OFF / SV42: OFF / SV43: ON
4. …
0 0 1
13
SV3F: OFF
A. …
… … 0
SV3F: ON
A. …
… … 1
14
PMV1 / PMV2
Displays the total opening data (decimal)
. P
15
PMV4
Displays the opening data (decimal)
…
. P
16
Oil judgment status
Normally
A [o L.]
B Initial display: [… … …], Oil judgment result display: [#.
.$]
[#]: Judgment result of Compressor 1, [
]: Judgment result of Compressor 2,
[$]: Judgment result of Compressor 3 (0: Appropriate, 1/2: Short)
<SW04> Push SW function: Displays the judgment result of each compressor
* Returns to normal display by
<SW05> push
A [L d.]
B Compressor 1 shortage being confirmed: [L … …]
Compressor 2 shortage being confirmed: [… L …]
Compressor 3 shortage being confirmed: [… … L]