102
(3)Outdoor cycle data display (Displayed on each outdoor unit)
SW01 SW02 SW03
Description
1
1
2
Pd pressure data
Displays the Pd pressure data (MPaG) in decimal
(MPaG: Approx. 1/10 of kg/cm
2
G)
A
B
P d.
.
2
Ps pressure data
Displays the Ps pressure data (MPaG) in decimal
P S.
3
PL pressure converted data
Displays the PL pressure converted value (MPaG) in decimal
P L.
.
4
TD1 sensor data
Displays the temperature sensor data (°C) in
decimal
• The symbol appears for 1 second and the
data for 3 seconds, alternately.
• If the data is minus, [–
] [
] appears.
Symbol
t d
1 … …
Data
.
5
TD2 sensor data
Symbol
t d
2 … …
Data
.
6
TD3 sensor data
Symbol
t d
3 … …
Data
.
7
TS sensor data
Symbol
t S
… … …
Data
.
8
TE1 sensor data
Symbol
t E
… … …
Data
.
9
TE2 sensor data
Symbol
t E
2 … …
Data
.
10
TL sensor data
Symbol
t L
… … …
Data
.
11
TO sensor data
Symbol
t o
… … …
Data
.
12
TK1 sensor data
Symbol
F 1
… … …
Data
.
13
TK2 sensor data
Symbol
F 2
… … …
Data
.
14
TK3 sensor data
Symbol
F 3
… … …
Data
.
15
TK4 sensor data
Symbol
F 4
… … …
Data
.
16
TK5 sensor data
Symbol
F 5
… … …
Data
.