9-8. Leakage / Clogging of the refrigerant cycle circuit
List of check codes displayed when a leakage / clogging error has occurred on the outdoor cycle
component / oil circuit component
<Clogging>
<Leakage>
Note:
“XX” indicates an auxiliary code.
Component
Error location
(See next page)
Unit where the
error occurred
Detected check code
Phenomenon
Outdoor PMV 1, 2
A
Own unit
High-pressure protection activation
Low-pressure protection activation
Discharge temperature error (TD1)
Discharge temperature error (TD2)
P20
H06
P03
P17
High-pressure rising
Low-pressure lowering
Discharge temperature rising
(compressor 1)
Discharge temperature rising
(compressor 2)
Check valve in the discharge area
B
Own unit
High-pressure protection error
High-pressure SW error
P20
P04-XX
Abnormal high-pressure
rising
Discharge pipe check valve
C
Own unit
High-pressure SW error
P04-XX
Abnormal high-pressure
rising
Oil circuit check valve
Capillary
Strainer
D
Own unit
Oil detection circuit error
Lower oil level detection protection
H16-XX
H07
Oil circuit error or shortage
judged
SV3A valve
E
Another connected
unit
Lower oil level detection protection
H07
Oil shortage
SV3B valve
F
Own unit
Lower oil level detection protection
H07
Oil shortage
SV3C valve
G
Another connected
unit
Lower oil level detection protection
H07
Oil shortage
SV3D valve
SV3D valve circuit
Capillary
Strainer
H
Own unit
Lower oil level detection protection
H07
Oil shortage
SV3E valve
I
Own unit
Oil detection circuit error
Lower oil level detection protection
H16-05
H07
Oil circuit error
Shortage judged
Oil shortage
Oil return distributer
J
Own unit
Lower oil level detection protection
H07
Oil shortage
SV3C bypass capillary
K
Own unit
Oil detection circuit error
H16-04
Oil circuit error
Component
Error location
(See next page)
Unit where the
error occurred
Detected check code
Phenomenon
Outdoor PMV 1, 2
A
Own unit
Outdoor compressor liquid
compression error
Lower oil level detection protection
P13
H07
Refrigerant hibernating
Another connected
unit
Discharge temperature error (TD1)
Discharge temperature error (TD2)
P03
P17
Discharge temperature rising
(compressor 1)
Discharge temperature rising
(compressor 2)
Check valve in the discharge area
B
Own unit
Lower oil level detection protection
Compressor breakdown
Compressor error (Lock)
H07
H01-XX
H02-XX
Refrigerant hibernating
Discharge pipe check valve
C
Own unit
Lower oil level detection protection
Compressor breakdown
Compressor error (Lock)
H07
H01-XX
H02-XX
Refrigerant hibernating
Oil circuit check valve
D
Own unit
Lower oil level detection protection
H07
Too much oil (Leaked side)
Oil shortage (Normal side)
SV3A valve
E
Own unit
Lower oil level detection protection
H07
Oil shortage
SV3C valve
G
Own unit
Lower oil level detection protection
H07
Shortage judged