11
Model with a humidifier
* Under 70 dBA
Model without a humidifier
* Under 70 dBA
MMD-VNK502HEXE-TR
MMD-VNK802HEXE-TR
MMD-VNK1002HEXE-TR
Type
Function
Cooling and heating dual purpose type
Unit configuration
Discrete type
Voltage
220-240 V~, 50 Hz
220-240 V~, 50 Hz
220-240 V~, 50 Hz
Equivalent HP
1.0
1.7
2.0
Refrigerant
R410A
Outdoor air
thermal load
handling
capacity
cooling
capacity
kw
4.10 (1.30)
6.56 (2.06)
8.25 (2.32)
heating
capacity
kw
5.53 (2.33)
8.61 (3.61)
10.92 (4.32)
Air Volume
m
3
/h
500
800
950
Notch
Extra high
High
Low
Extra high
High
Low
Extra high
High
Low
Power consumption
W
305
285
240
530
485
350
575
565
520
External Static Pressure
Pa
95
85
95
105
85
90
110
90
115
Humidification level
kg/h
3.0
5.0
6.0
Sound pressure level
dB
36.5
35.5
33.5
40.0
39.0
38.0
42.0
41.0
39.0
Sound power level
dBA
*
*
*
External
dimensions
Height
mm
430
430
Width
mm
1140
1189
Depth
mm
1690
1739
Weight
kg
91
111
112
MMD-VN502HEXE-TR
MMD-VN802HEXE-TR
MMD-VN1002HEXE-TR
Type
Function
Cooling and heating dual purpose type
Unit configuration
Discrete type
Voltage
220-240 V~, 50 Hz
220-240 V~, 50 Hz
220-240 V~, 50 Hz
Equivalent HP
1.0
1.7
2.0
Refrigerant
R410A
Outdoor air
thermal load
handling
capacity
cooling
capacity
kw
4.10 (1.30)
6.56 (2.06)
8.25 (2.32)
heating
capacity
kw
5.53 (2.33)
8.61 (3.61)
10.92 (4.32)
Air Volume
m
3
/h
500
800
950
Notch
Extra high
High
Low
Extra high
High
Low
Extra high
High
Low
Power consumption
W
300
280
235
505
465
335
550
545
485
External Static Pressure
Pa
120
105
115
120
100
105
135
120
105
Sound pressure level
dB
37.5
36.5
34.5
41.0
40.0
38.0
43.0
42.0
40.0
Sound power level
dBA
*
*
*
External
dimensions
Height
mm
430
430
Width
mm
1140
1189
Depth
mm
1690
1739
Weight
kg
84
100
101
Summary of Contents for MD-VNK802HEXE
Page 120: ...118 11Owner s Manual Excerpt ...
Page 137: ...135 12Installation Manual Excerpt ...