Installation Manual
On the outside of the unit, do not allow the wire for the remote controller (communication wire) and the wire for
AC220-240 V to come into contact or put them together in one electrical conduit; otherwise, the control system may
have trouble due to noise.
Item
Model name
MMD-
Communication line
Indoor / Outdoor inter-unit wiring (*2) (2
cables)
Central control line wiring (*3) (2 cables)
Remote controller wiring (*4)
Air to Air Heat
Exchanger with
DX Coil Unit
VNK502HEXE
VN502HEXE
VNK802HEXE
VN802HEXE
(Up to 1000 m)
2-core, non-polarity shield wire: 1.25 mm
2
(Up to 2000 m)
2-core, non-polarity shield wire: 2.00 mm
2
2-core, non-polarity: 0.5 to 2.0 mm
2
VNK1002HEXE
VN1002HEXE
VNK1002HEXE2
VN1002HEXE2
(*2) (*3)
• 2-core with non-polarity wires are used for the Indoor / Outdoor inter-unit wiring and Central controller wiring.
• To prevent noise trouble, use 2-core shield wire.
• The length of the communication line means the total length of the inter-unit wire length between indoor and outdoor units added with the
central control system wire length.
(*4)
• 2-core with non-polarity wire is used for wiring of the remote controller wiring and group remote controllers wiring.
Remote controller wiring, remote controller inter-unit wiring
2-core, non-polarity: 0.5 mm
2
to 2.0 mm
2
Total wire length of remote controller wiring and remote
controller inter-unit wiring = L + L1 + L2 + ··· Ln
For wired type only
Up to 500 mm
When wireless type is included
Up to 400 mm
Total wire length of remote controller inter-unit wiring = L1 + L2 + ··· Ln
Up to 200 mm
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Remote
controller
Remote controller
wiring
Remote controller inter-unit wiring
(Up to 8 units)