175
Installation Manual
Ventilation Fan speed setting
The setting of the ventilation Fan speed can be changed when using the remote controller for air conditioners
(RBC-AMT32E, RBC-AMS41E) or using the system without the remote controller.
* Adjusting this setting is necessary for the header unit when using a system equipped with the Air to Air Heat
Exchanger with DX Coil Unit only (RBC-AMT32E can not be used.), and for the Air to Air Heat Exchanger with
DX Coil Unit with the smallest address number when using a system equipped with the Air to Air Heat Exchanger
with DX Coil Unit and air conditioners.
* When the remote controller NRC-01HE is installed, this setting is invalid. (The remote controller can be used for
operation.)
• Select [EB] in step 3 on page 169.
• Select a value from the table on the below in step 4 on page 170.
* When [0004] is selected, adjust setting of the unbalanced ventilation Fan speed (Code: 48).
Setting for changing the operation output
Terminals 1 and 2 for external devices can be used to connect an auxiliary fan or to use the operation output for
operating external devices connected to the terminal. It can be specified when the operation output is used.
* Apply this setting for the Air to Air Heat Exchanger with DX Coil Unit to which an external device is connected.
• Select [ED] in step 3.
• Select a value from the table below in step 4.
* Contact is off during switching the damper (Heat exchange mode / Bypass mode) regardless of the selected
value.
Code
SET DATA
0002
0003
0004
EB
Changing the ventilation
amount
High
(Factory default)
Low
Unbalanced
Code
SET DATA
0000
0001
0002
0003
0004
ED
Changing the
operation
output
ON during
normal
operation
(Factory
default)
ON during
normal
operation or
nighttime heat
purge operation
ON during
nighttime heat
purge operation
ON when SA
fan is running
ON when EA
fan is running
0000: Contact is on only during normal operation.
* Contact is off during nighttime heat purge operation.
* Contact is off during cold mode (while the temperature is below -10 °C)
0001: Contact is on during normal operation and nighttime heat purge operation.
* Contact is off when nighttime heat purge operation is on standby. (paused before the monitoring operation of
nighttime heat purge operation starts)
* Contact is off during cold mode (while the temperature is below -10 °C)
0002: Contact is on during nighttime heat purge operation.
* Contact is off during normal operation or when nighttime heat purge operation is on standby. (paused before the
monitoring operation of nighttime heat purge operation starts)
* Contact is off during cold mode (while the temperature is below -10 °C)
0003: Contact is on only when SA fan is running.
0004: Contact is on only when EA fan is running.