21
4
Ventilation
mode switch
(Continued)
2) Without remote controller, RBC-AMT32 remote controller compatible
• The ventilation mode can be switched depending on CODE (DN) [EA]
5
Ventilation
fan speed
switch
1) The ventilation fan speed is switched by the request from the remote controller.
* Unbalance needs to be set in CODE (DN) [48].
2) Without remote controller, RBC-AMT32 remote controller compatible
• The ventilation fan speed can be changed depending on CODE (DN) [EB]
CODE No.
[48][EB]
6
Room
temperature
control
1) Temperatures adjusted by remote controller (°C)
2) The HEAT temperature can be adjusted depending on CODE (DN) [06].
Factory setting
3) In addition to the above, the Air to Air Heat Exchanger with DX Coil Unit adjusts the
temperature of its own.
Factory setting
* Do not change the settings.
CODE No.
[06][C9][CA]
Heat suction
temperature shift
(Except during remote
controller thermo)
Follow the normal indoor
unit setting.
No.
Item
Specification outline
Remarks
SET DATA
2
3
Ventilation mode
Heat
exchange
Automatic
By remote controller
Description
High
Operate supply air / exhaust air in High
Low
Operate supply air / exhaust air in Low
Unbalance (*)
Operate supply air in High, exhaust air in Low
(Supply air > Exhaust air)
Operate supply air in Low, exhaust air in High
(Supply air < Exhaust air)
SET DATA
0
1
2
Unbalanced fan
speed ventilation
Invalid
Valid
(Supply air >
Exhaust air)
Valid
(Supply air <
Exhaust air)
SET DATA
2
3
4
Ventilation fan speed
High
Low
Unbalance
Cool / Dry
Heat
18 - 29
18 - 29
SET DATA
0
2
4
6
Temperature setting
correction
+0 °C
+2 °C
+4 °C
+6 °C
SET DATA
2
Temperature setting
correction
+2 °C
Cool / Dry
Heat
CODE No.
[ C9 ]
[ CA ]
SET DATA
0 - 7
0 - 7
Temperature setting
correction
-0 °C to -3.5 °C
(0.5 °C - interval)
+0 °C to +3.5 °C
(0.5 °C - interval)
Cool / Dry
Heat
SET DATA
4
5
Temperature setting
correction
-2.0 °C
+2.5 °C