53
Check code list (Outdoor)
(Example: Detected on the SMMS-i standard & thermal outdoor interface)
Check code
Typical cause of error
Description
7-segment display of outdoor unit
Local remote
controller &
TCC-LINK
central controller
Sub code
E06
Number of indoor units for normal
reception
E06
Number of indoor units decreasing
No communication can be established any more. (The number of
connected indoor units has decreased.)
E07
–
(E04)
Central communication circuit error
No signal can be sent to the indoor unit. (No communications from
outdoor unit to indoor unit)
E08 Duplicate indoor unit No.
(E08)
Duplicate indoor addresses
There are multiple indoor units with the same address. (May also
be detected on the indoor unit)
E12
01: Central control
02: Communications between
outdoor units
E12
Automatic address start error
The automatic indoor address operation has been performed
during automatic address setting of another line.
The automatic outdoor address operation has been performed
during indoor automatic address setting.
E15
–
E15
No indoor unit during automatic
address
No data is received from the outdoor unit during automatic
address.
E16
00: Over capacity
01 ~: Number of connected units
E16
Number of connected units /
Capacity exceeded
The total capacity of indoor units has been exceeded. (Over 135 %
of total capacity of outdoor unit)
E19
00: No center unit
02: Multiple center units
E19
Unusual number of center outdoor
units
There are no or multiple center outdoor units in a line.
E20
01: Outdoor connections of another
line
02: Indoor connections of another
line
E20
Connections of another line during
automatic address
An indoor unit of another line has been detected during automatic
address setting.
E21
00: Number of duplicate header
units
02: No header unit
E21
Unusual number of thermal header
units
There are no or multiple thermal header units in a line.
E22
–
E22
Number of thermal units decreasing
No communication can be established any more. (The number of
connected thermal units has decreased.)
E23
–
E23
Transmission error between
outdoor units
No signal can be sent to another outdoor unit.
E25
–
E25
Duplicate terminal outdoor address
settings
The manually set terminal outdoor addresses are duplicate.
E26
Outdoor address with reception
error
E26
Number of connected outdoor units
decreasing
No communication can be established any more. (The number of
connected terminal outdoor units has decreased.)
E28 Detected outdoor unit No.
E28
Terminal outdoor error
The center outdoor unit has detected an error of the terminal
outdoor unit. (Details displayed for the terminal outdoor unit)
E31
E31
IPDU communication error
There is no communication of each IPDU (PC board) in the inverter
box.
F04
–
F04
Outdoor discharge temperature
sensor (TD1) error
Open-circuit or short-circuit of the outdoor discharge temperature
sensor (TD1) was detected.
F05
–
F05
Outdoor discharge temperature
sensor (TD2) error
Open-circuit or short-circuit of the outdoor discharge temperature
sensor (TD2) was detected.
F06
01: TE1
02: TE2
F06
Outdoor heat exchange
temperature sensor (TE1, TE2)
error
Open-circuit or short-circuit of the heat exchange temperature
sensor (TE1, TE2) was detected.
F07
–
F07
Outdoor liquid temperature sensor
(TL) error
Open-circuit or short-circuit of the outdoor liquid temperature
sensor (TL) was detected.
F08
–
F08
Outdoor temperature sensor (TOA)
error
Open-circuit or short-circuit of the outdoor temperature sensor
(TOA) was detected.
F11
–
F11
F12
–
F12
Outdoor suction temperature
sensor (TS1) error
Open-circuit or short-circuit of the outdoor suction temperature
sensor (TS1) was detected.
F15
–
F15
Miswiring of outdoor temperature
sensor (TE1, TL) error
Miswiring of the temperature sensor (TE1, TL) was detected.
F16
–
F16
Miswiring of outdoor pressure
sensor (Pd, Ps) error
Miswiring of the outdoor pressure sensor (Pd, Ps) was detected.
A3-IPDU
Fan
IPDU
A3-IPDU
Fan
IPDU
1
2
3
1
2
3
01 O
0A
O
O
02
O
0B O
O
O
03 O
O
0C
O
O
04
O
0D O
O
O
05 O
O
0E
O
O
O
06
O
O
0F O
O
O
O
07 O
O
O
O: IPDU error
08
O
09 O
O
Summary of Contents for MD-VNK802HEXE