59
E12
E12
01:
Central control
02:
Communications
between outdoor
units
I/F
Automatic
address start
error
All stopped
• The automatic indoor address
start setting has been configured
during automatic address setting
of another refrigerant line device.
• The automatic outdoor address
start setting has been configured
during indoor automatic address
setting.
Set the address again after
disconnecting communications with
another refrigerant line.
E15
E15
–
I/F
No indoor unit
during
automatic
address
All stopped
The indoor unit cannot be detected
when the automatic indoor address
start setting is configured.
• Check the connection of the
communication line between
indoor and outdoor.
• Check the indoor power line error.
• Check the peripheral noise.
• Check the blackout.
• Check the indoor PC board error.
E16
E16
00:
Over capacity
01 ~:
Number of
connected units
I/F
Number of
connected units
/ Capacity
exceeded
All stopped
• The total capacity of the indoor
unit has exceeded 135 % of the
total capacity of the outdoor unit.
Note:
If this code appears after
configuring the backup setting for
outdoor unit failure, configure the
setting for "Over capacity" not
detected".
<"Over capacity" not detected>
Turn on [SW09 / Bit 2] on the center
outdoor I/F board.
• More than 48 indoor units have
been connected.
• Check capacity of indoor unit
connection.
• Check capacity of indoor unit
horse power.
• Check outdoor unit horse power
setting.
• Check number of connected
indoor units.
• Check the outdoor PC board (I/F)
error.
E18
–
–
Indoor
Indoor header -
follower
communication
error
Only the target
unit stopped
Regular communication is not
possible between the header and
follower indoor units.
• Check remote controller wiring.
• Check indoor power wiring.
• Check the indoor PC board.
E19
E19
00:
No center unit
02:
Multiple center
units
I/F
Unusual
number of
center outdoor
units
All stopped
• There are multiple center outdoor
units in a line.
• There are no center outdoor units
in a line.
The center outdoor unit is
connected to the indoor - outdoor
wiring (U1, U2).
• Check the connection of the
communication line between
indoor and outdoor.
• Check the outdoor PC board (I/F)
error.
E20
E20
01:
Outdoor
connections of
another line
02:
Indoor
connections of
another line
I/F
Connections of
another line
during
automatic
address
All stopped
Another line device is connected
when the automatic indoor address
start setting is configured.
Perform the automatic address
setting procedure of "Address
settings" to cut the line wires.
E23
E23
–
I/F
Transmission
error between
outdoor units
All stopped
No signal can be sent from another
outdoor unit for 30 seconds or
longer.
• Check outdoor unit power.
(Whether powered on)
• Check wire connection between
outdoor units.
• Check the connector connection
for outdoor PC board
communications.
• Check the outdoor PC board (I/F)
error.
• Check terminal resistance
settings of communications
between outdoor units.
E25
E25
–
I/F
Duplicate
terminal outdoor
address settings
All stopped
More than one outdoor unit are
assigned to the same outdoor
address manual setting.
Note:
Do not set the outdoor address
manually.
E26
E26
Outdoor address
with reception
error
I/F
Number of
connected
outdoor units
decreasing
All stopped
Signals are not returned for a given
time from the outdoor unit.
• While setting the outdoor backup.
• Check outdoor unit power.
(Whether powered on)
• Check wire connection between
outdoor units.
• Check the connector connection
for outdoor PC board
communications.
• Check the outdoor PC board (I/F)
error.
Check code
Location
of
detection
Check code
name
System status
Error detection conditions
Items to check (locations)
Local
remote
controller
7-segment display of
outdoor unit
Check
code
Sub code