63
H07
H07
–
I/F
Lower oil level
detection
protection
All stopped
The running compressor has
detected low oil level for
approximately 2 hours.
<Check for all outdoor units in the
line>
• Open and check the service valve
of balance pipe.
• Check the connection and
installation of the TK1, TK2, TK3,
TK4, and TK5 sensors.
• Check the TK1, TK2, TK3, TK4,
and TK5 sensor resistant
characteristics.
• Check gas and oil leakage in the
same line.
• Check the hibernating refrigerant
in the compressor case.
• Check the SV3A, SV3B, SV3C,
SV3D, SV3E, and SV3F valve
error.
• Check the clogging of the oil
separator oil return circuit.
• Check the oil circuit clogging.
H08
H08
01:
TK1 sensor error
02:
TK2 sensor error
03:
TK3 sensor error
04:
TK4 sensor error
05:
TK5 sensor error
I/F
Oil level
detection
temperature
sensor error
All stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
of the TK1 sensor.
• Check the TK1 sensor resistant
characteristics.
• Check the outdoor PC board (I/F)
error.
All stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
of the TK2 sensor.
• Check the TK2 sensor resistant
characteristics.
• Check the outdoor PC board (I/F)
error.
All stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
of the TK3 sensor.
• Check the TK3 sensor resistant
characteristics.
• Check the outdoor PC board (I/F)
error.
All stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
of the TK4 sensor.
• Check the TK4 sensor resistant
characteristics.
• Check the outdoor PC board (I/F)
error.
All stopped
The sensor resistance is infinite or
zero (open circuit or short circuit).
• Check the connector connection
of the TK5 sensor.
• Check the TK5 sensor resistant
characteristics.
• Check the outdoor PC board (I/F)
error.
H15
H15
–
I/F
Misconnection
of outdoor
discharge
temperature
sensor (TD2)
All stopped
The discharge temperature (TD2)
does not rise while the compressor
2 is running.
• Check installation of the TD2
sensor.
• Check the connector connection
and wiring of the TD2 sensor.
• Check the TD2 sensor resistant
characteristics.
• Check the outdoor PC board (I/F)
error.
Check code
Location
of
detection
Check code
name
System status
Error detection conditions
Items to check (locations)
Local
remote
controller
7-segment display of
outdoor unit
Check
code
Sub code