116
10-4. Check Code and Check Position Displayed on the Remote Controller and Outdoor Unit
(7-Segment Display of Interface)
Check code
Outdoor 7-segment display
Wired
remote
controller Check code Auxiliary code
AI-NET
central control
remote controller
Detected
position
Check code name
Status
Error detection condition
Check item (position)
E01
—
—
—
Remote
controller
Communication error between
indoor and remote controller
(Detected at remote controller side)
Corresponding
unit only stops.
Communication interrupted
between indoor P.C. board
and remote controller.
• Check remote controller inter-unit cable (A/B).
• Check disconnection, connector contact error.
• Check indoor power supply.
• Check indoor P.C. board error.
• Check remote controller address setup.
(When two remote controllers operate)
• Check remote controller P.C. board.
E02
—
—
—
Remote
controller
Remote controller sending error
Corresponding
unit only stops.
Signal could not be sent from
remote controller to indoor
unit.
• Check the communication wire of remote controller: Exchange remote
controller.
E03
—
—
97
Indoor unit Communication error between
indoor and remote controller
(Detected at indoor side)
Corresponding
unit only stops.
No communication from
remote controller (including
wireless) and communication
adapter.
• Check remote controller and communication adapter wiring.
E04
—
—
4
Indoor unit Indoor/outdoor communication
circuit error
(Detected at indoor side)
Corresponding
unit only stops.
Indoor unit does not receive
communication from outdoor
unit.
• Check power-ON order of indoor/outdoor.
• Check indoor address setup.
• Check inter-unit cabling between indoor and outdoor.
• Check outdoor end terminal resistance setup (SW30-2).
E06
E06
No. of indoor
units which
received signal
normally
4
I/F
Decreased number of indoor units
All stop
When signal is not sent for a
certain period from the indoor
unit which has been used to
send signals, [E06] is
normally displayed.
• Check the power supply of indoor unit. (Power-ON)
• Check connection of communication line between indoor and outdoor.
• Check connector connection for communication in indoor P.C. board.
• Check connector connection for communication in outdoor P.C. board.
• Check indoor P.C. board failure.
• Check outdoor P.C. board (I/F) failure.
—
E07
—
—
I/F
Indoor/outdoor communication
circuit error
(Detected at outdoor side)
All stop
Transmission from outdoor to
indoor cannot continue for 30
seconds.
• Check outdoor terminator resistor setup (SW30-2).
• Check the communication connection between indoor and outdoor.
E08
E08
Duplicated
indoor
addresses
96
Indoor
I/F
Duplicated indoor addresses
All stop
Multiple indoor unit address
setup are duplicated.
• Check indoor address.
• Check the change of remote controller connection (Group / individual)
after setup of indoor address.
E09
—
—
99
Remote
controller
Duplicated master remote
controllers
Corresponding
unit only stops.
In 2-remote controller control
(including wireless), both are
setup as master
(Header indoor unit stops and
other indoor unit is operating.)
• Check remote controller setup.
• Check remote controller P.C. board.
E10
—
—
CF
Indoor unit Communication error between
indoor P.C. board assembly
Corresponding
unit only stops.
There is any trouble in power
line.
• Indoor P.C. board failure