64
Table: Function selecting item code (DN)
(Items necessary to perform the applied control at the local site are described.)
DN
01
02
03
04
06
0d
0E
0F
10
11
12
13
14
19
1E
28
29
2A
2E
30
31
32
33
40
5d
Item
Filter display delay
timer
Dirty state of filter
Central control
address
Specific indoor unit
priority
Heating temp shift
Existence of [AUTO]
mode
Follows operation
mode of the header
unit
Cooling only
Type
Indoor unit capacity
Line address
Indoor unit address
Group address
Louver type
(Adjustment of air
direction)
Temp difference of
[AUTO] mode
selection COOL
→
HEAT, HEAT
→
COOL
Automatic restart of
power failure
Operation condition
of humidifier
Selection of option/
error input (CN70)
HA terminal (CN61)
select
Automatic elevating
grille
Ventilating fan
control
TA sensor selection
Temperature unit
select
Drain pump control
Description
0000 : None
0001 : 150H
0002 : 2500H
0003 : 5000H
0004 : 10000H
0000 : Standard
0001 : High degree of dirt (Half of standard time)
0001 : No.1 unit
to
0064 : No.64 unit
0099 : Unfixed
0000 : No priority
0001 : Priority
0000 : No shift
0001 : +1°C
0002 : +2°C
to
0010 : +10°C
(Up to +6 recommended)
0000 : Provided
0001 : Not provided (Automatic selection from connected outdoor unit)
0000 : Does not follow
0001 : Follows
0000 : Heat pump
0001 : Cooling only (No display of [AUTO] [HEAT])
0000 : (1-way air discharge cassette)
0001 : (4-way air discharge cassette) to 0037
0000 : Unfixed
0001 to 0034
0001 : No.1 unit
to
0030 : No.30 unit
0001 : No.1 unit
to
0064 : No.64 unit
0000 : Individual
0001 : Header unit of group
0002 : Follower unit of group
0000 : Not provided
0001 : Swing only
0004 : [4-way Air Discharge Cassette type] and [Under Ceiling type]
0000 : 0 deg
to
0010 : 10 deg
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
0000 : None
0001 : Restart
0000 : Usual
0001 : Condition ignored
(Detection control for heat exchanger temperature)
0000 : Filter input
0001 : Alarm input (Air washer, etc.)
0002 : None
0000 : Usual
0001 : Leaving-ON prevention control
0000 : Unavailable
0001 : Available
0000 : Unavailable
0001 : Available
0000 : Body TA sensor
0001 : Remote controller sensor
0000 : °C (at factory shipment)
0001 : °F
0000 : None
0001 : Pump ON
0002 : None
0003 : Pump OFF
At shipment
According to type
0000 : Standard
0099 : Unfixed
0000 : No priority
0002 : +2°C
(Floor type 0000: 0°C)
0001 : Not provided
0000 : Not provided
0000 : Heat pump
According to model type
According to capacity type
0099 : Unfixed
0099 : Unfixed
0099 : Unfixed
According to type
0003 : 3 deg
(Ts±1.5)
0000 : None
0000 : Usual
0002 : None
0000 : Usual
(HA terminal)
0000 : Unavailable
0000 : Unavailable
0000 : Body TA sensor
0000 : °C
0003 : Pump OFF
0000 : Standard
Timer set
(Wired remote
controller)
Anti-ceiling
smudging control
60
62
0000 : Available (Operable)
0001 : Unavailable (Operation prohibited)
0000 : Clear
0000 : Available
4- way Air Discharge
Cassette type only
Indoor unit type
4-way Air Discharge
Cassette
MMU-AP
✻✻✻
1H
Compact 4-way Air
MMU-AP
✻✻✻
1MH
Discharge Cassette
1-way Air Discharge
MMU-AP
✻✻✻
2SH
Cassette
Concealed Duct
MMU-AP
✻✻✻
1BH
Standard
Slim Duct
MMU-AP
✻✻✻
1SPH
High ceiling selection (Air volume selection)
Item
High ceiling
Filter
High ceiling
High ceiling
External static
pressure
External static
pressure
Set up data
0
1
2
3
6
Standard
High ceiling
—
High ceiling
—
(1)
(3)
Standard
Super long
—
High efficiency
—
life filter
filter
Standard
—
High ceiling
High ceiling
—
(2)
(3)
Standard
High ceiling
—
High ceiling
—
(1)
(3)
40Pa
70Pa
—
100Pa
20Pa
10Pa
20Pa
—
35Pa
50Pa