11
7
ELECTRIC WORK
WARNING
1. Using the specified wires, ensure to connect the wires, and fix wires securely so that the
external strength of the wires do not transmit to the connecting part of the terminals.
Incomplete connection or fixation may cause fire, etc.
2. For electric work, strictly follow to the Local Regulation in each country and the Installation
Manual, and use an exclusive circuit.
Capacity shortage of power circuit or incomplete installation may an electric shock or ftre.
REQUIREMENT
• Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe.
The coating may melt resulted in an accident.
• After connecting wires to the terminal blocks, provide a trap and fix wires with the wire clamp.
• Store the refrigerant piping line and control wiring line in the same line.
• Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes.
Wire connections
Use the supplied, dedicated wires.
REQUIREMENT
• Check that power is not supplied to the indoor unit before connecting wires.
• Be sure to put wires though the wire connecting ports on the PMV Kit and the indoor unit.
For this product, the connector conversion cable (Accessory) is used according to the indoor unit to
be connected.
For the corresponding unit and how to use the conversion cable, refer the following description.
Indoor unit which connector conversion cable is not used
High Wall Type 2 series (MMK-AP0092H, MMK-AP0122H)
Remove the connector conversion cable which is attached to the connection cable (11m) out of the box.
Indoor unit which connector conversion cable is used
Indoor unit except above indoor units
Connection cable
Connection cable
Connector conversion cable
Connector conversion cable