118
18
Trial Operation
Service Support Function
(1) Trial cooling operation function
This function is to change the modes of all the indoor units connected to an identical system
collectively to trial cooling operation modes using the switch on interface P.C. board of the
inverter type outdoor unit.
Operation procedure
Operation
7 Segment LED
[A]
7 Segment LED
[B]
SW01, 02, 03: Rotary switch
SW04, 05: Push switch
SW08: Dip switch
Set SW01 on the interface P.C. board of the inverter
outdoor unit to 2 , SW02 to 5, and SW03 to 1.
Push the push-switch SW04 on the P.C. board of the
inverter outdoor unit for 2 seconds or more.
Check that mode on the remote controller of the indoor
unit to be operated is trial cooling operation mode.
(L is displayed.)
Check that -C is displayed on the 7 segment LED [B]
of the interface P.C. board of the inverter outdoor unit.
Return SW01 to 1, SW02 to 1, and SW03 to 1 on
the interface P.C. board of the inverter outdoor unit.
Operation check
Stop/Completion
Power ON