13
4
Parts Specifications
Indoor Units
No.
PARTS NAME
TYPE
SPECFICATIONS
1
Fan Motor
MMF-230-36A
Output (rated) 36W, 6 pole, 230V, 1 Phase 50Hz
2
Running Capacitor – fan motor EVM45M305UF
AC 450V, 3.0µF
3
Pulse Motor Valve
EDM-B60YPTF-7B-A Capacity: 60
4-Way Cassette: MM-U140
No.
PARTS NAME
TYPE
SPECFICATIONS
1
Fan Motor
MMF-230-36A
Output (rated) 36W, 6 pole, 230V, 1 Phase 50Hz
2
Running Capacitor – fan motor EEP2W255HQA113 AC 450V 2.5µF
3
Pulse Motor Valve
EDM-B40YPTR-7B-A Capacity: 40
4-Way Cassette: MM-U112
No.
PARTS NAME
TYPE
SPECFICATIONS
1
Fan Motor
MMF-230-28A
Output (rated) 28W, 6 pole, 230V, 1 Phase 50Hz
2
Running Capacitor – fan motor EEP2W205HQA107 AC 450V 2.0µF
3
Pulse Motor Valve
EDM-B40YPTR-7B-A Capacity: 40
4-Way Cassette: MM-U080
No.
PARTS NAME
TYPE
SPECFICATIONS
1
Fan Motor
MMF-230-28A
Output (rated) 28W, 6 pole, 230V, 1 Phase 50Hz
2
Running Capacitor – fan motor EEP2H105HQA105 AC 500V 1.0µF
3
Pulse Motor Valve
EDM-B40YPTR-7B-A Capacity: 40
4-Way Cassette: MM-U056
No.
PARTS NAME
TYPE
SPECFICATIONS
4
Transformer
TT-03-1
DC 16.3V 0.5A/AC 11.6V 0.15A
5
Pulse Motor
EDM-MD12TF-3
DC12V
6
Pressure Sensor
150/100NH6-D
Power Voltage DC 12V
7
Sensor for room temperature
TA
Maximum input
°C
25
50
38mA (at 25°C)
k
Ω
10
3.45
8
Sensor for heat exchanger
Tc1
Maximum input
°C
-12
0
25
50
34mA (at 25°C)
k
Ω
62.3 32.8 10
3.6
9
Sensor for heat exchanger
Tc2
Maximum input
°C
0
25
50
26mA (at 25°C)
k
Ω
34.6 10
3.4
10
Control PCB
CM00C02
AC 220-240V
11
Power PCB
P00RC01
AC 220-240V
4-Way Cassette: MM-U140, MM-U112, MM-U080, MM-U056
Summary of Contents for MM-A0160HX
Page 1: ...Service Manual Air Conditioner Multi Split Type System Modular Multi System HFCR407C A90 0130 ...
Page 2: ......
Page 133: ...134 20 Additional Literature and Contacts ...
Page 134: ...135 20 Additional Literature and Contacts ...
Page 135: ...TOSHIBA AIR CONDITIONING www toshiba aircon co uk MADE IN UK A90 0130 Revised April 2001 ...