32
10
Refrigeration Cycle Schematic
Indoor Units
32
Heat exchanger
Strainer
Strainer
Pressure
sensor
Check
joint
TC1
Gas
sensor
PMV (D)
TC2
Liquid
sensor
Refrigerant Pipe
(liquid) (A)
Capillary
tube (B)
Distributor
strainer
Refrigerant
Pipe (Gas) (C)
Model
Ø(A) mm
Capillary Ø(B) mm
Ø(C) mm
PMV (D) Code
MM-B056
6.4 (3/8”)
Ø1.7x150Lx3
12.7 (1/2”)
40
MM-B080
9.5 (3/8”)
Ø2.6x200Lx4, Ø2.6x400Lx2
15.9 (5/8”)
40
MM-B112
9.5 (3/8”)
Ø2.2x200Lx6
19.0 (3/4”)
40
MM-B140
9.5 (3/8”)
Ø2.2x200Lx6
19.0 (3/4”)
60
MM-SB028
6.4 (3/8”)
Ø1.7x250Lx2
12.7 (1/2”)
25
MM-U056
6.4 (3/8”)
Ø2.0x200Lx3
12.7 (1/2”)
40
MM-U080
9.5 (3/8”)
2.6x(150Lx2), (200Lx3), (400Lx1)
15.9 (5/8”)
40
MM-U112
9.5 (3/8”)
2.6x(200Lx6), (300Lx2), (500Lx2)
19.0 (3/4”)
40
MM-U140
9.5 (3/8”)
2.6x(200Lx6), (300Lx2),(500Lx2)
19.0 (3/4”)
60