Outline of Control
Outdoor Unit
Item
Operation explanation and applied data, etc.
Remarks
1b. Pulse motor
valve (PMV)
control
(1) PMV B control
The purpose of PMV B control is to control the liquid
refrigerant bypass by limiting discharge
temperature or compressor internal temperature
increase.
1) Opening is controlled with pulses from 0 ~ 500.
2) PMV opening is controlled with temp. detected
by TS/TD sensors.
3) PMV openings are fully closed during thermostat-
OFF, operation stop, and emergency stop.
2a. Outdoor fan
control
(1) Cooling fan control
1) In a specified time when cooling operation is
activated, the master outdoor unit controls the
outdoor fan speed (no. of fan driving waves) by Pd
pressure. The slave outdoor unit controls the
outdoor fan speed with temperature detected by
TE sensor.
*
PD pressure is maintained between 14.5 ~ 18
kgf/cm
2
G by the cooling fan control. The no. of
waves can be controlled between 0 wave (STOP) to
16 waves (all waves).
[+1 wave/20 sec ]
From 2 waves to
Max. no. of waves
[Hold ]
From 1 wave to
Max. no. of waves
[-1 wave/20 sec ]
In down time:
From 15 waves to 1 wave
In up time:From 0 wave to 1 wave
[+1 wave/20 sec ]
(Up to 5 waves)
Interval [0 wave ]: 180 sec
control
[1 wave ]:
30 sec
Max.
16 waves
[
[
]
]
Pd pressure
(kgf/cm
2
G) 22
21
19
18
17
16
15
14
13
12
11
1a. Electronic
expansion
valve (PMV)
control
(1) PMV A control (PMV x 2)
1) The PMV (pulse motor valve) is controlled
between 100 ~ 1000 pulses during the
operation.
2) The PMV is fully open during the cooling
operation (PMV A1 = 500 pulses,
PMV A2 = 500 pulses).
3) During the heating operation, the opening rate is
determined by the temperature which the TS/TD
sensor detects and the pressure rate which PS
detects (Super heat control).
4) The PMV is fully open when the thermostat is off,
when the operation is switched off or when the
operation is ceased under abnormal
circumstances.
Min.
Mid.
Max.
PMV
opening
rate
1000
550
500
100
50
PMV A2
PMV A1
Summary of Contents for MM-A0160HX
Page 1: ...Service Manual Air Conditioner Multi Split Type System Modular Multi System HFCR407C A90 0130 ...
Page 2: ......
Page 133: ...134 20 Additional Literature and Contacts ...
Page 134: ...135 20 Additional Literature and Contacts ...
Page 135: ...TOSHIBA AIR CONDITIONING www toshiba aircon co uk MADE IN UK A90 0130 Revised April 2001 ...