38
11
Outline of Control
Outdoor Units
Item
Operation explanation and applied data, etc.
Remarks
9. Compressor
winding
heating control
This control is to prevent stagnation of refrigerant in
the compressor case by a supply of current to heat the
windings while the inverter compressor is off. This
control is executed by the inverter outdoor unit only. If
the supply of current is not turned on for a specified
time before trial operation, when installation work has
finished, a fault of the compressor may occur. If the
power source is interrupted for a period of time it is
necessary to switch power to the system for a minimum
of 24 hours before commencing system operation
(1) Control conditions
Compressor stops and TD < 35°C.
(2) Contents of control
This control is executed by temperature detected by
TK3 sensor as shown in the following figure.
NOTE:
Switching may be heard during heat winding
operation, but it is not an error/fault.
10. Crank case
heater control
This control is executed by the fixed-speed unit only.
(1) Control contents
• This control is switched off when TK3 sensor
detected 40°C or higher temperature, and
switched on when TK3 sensor detected 35°C or
lower temperature.
• After the compressor status changed from OFF to
ON, ON status continues for 10 minutes.
A zone
B zone
C zone
Intermittent
Continuous
switch-on power
No
switch-on power
ON: 10 minutes
switch-on power
OFF: 5 minutes
TK3
40°C
34°C
25°C
C zone
B zone
A zone
Summary of Contents for MM-A0160HX
Page 1: ...Service Manual Air Conditioner Multi Split Type System Modular Multi System HFCR407C A90 0130 ...
Page 2: ......
Page 133: ...134 20 Additional Literature and Contacts ...
Page 134: ...135 20 Additional Literature and Contacts ...
Page 135: ...TOSHIBA AIR CONDITIONING www toshiba aircon co uk MADE IN UK A90 0130 Revised April 2001 ...