43
11
Outline of Control
Indoor Units
Item
Operation explanation and applied data, etc.
Remarks
1. Power source
is reset
(1) Automatic remote controller function setup
Based upon the result of selecting indoor unit
model, setup and display range of the remote
controller.
• Operation mode
range Air volume
select/ Louver
presence
• Ts : setup temp
(R/C).
TA: Room temp
(Ambient).
2. Operation
select
(1) Based upon the operation select command from the
remote controller or central controller, the operation
mode is selected.
3. Room temp.
control
(1) Adjustment range
(2) Operation point with compressor-OFF
(3) Operation temp. precision ± 1°C
(4) Differential 1°C
4. Automatic
capacity
control
(1) Based upon difference between Ta and Ts, the
operation frequency is indicated to the outdoor unit.
NOTE:
The operation frequency in the above zone differs
according to horse power or protective control of the
outdoor unit.
5. Capacity
correction
control
(1) Frequency correction control
Frequency of the outdoor unit is corrected so that
the present capacity reaches to the certain specified
capacity.
(2) PMV opening correction control
PMV opening is corrected so that the refrigerant
status of the indoor unit becomes most appropriate
to the demand.
Remote controller command
Control outline
STOP
Stops air conditioner
FAN Fan
operation
COOL Cooling
operation
HEAT
Heating operation
In cooling/heating
Remote controller setup temp.
18 to 29°C
Operation temp.
18 to 29°C
COOL
Compressor-OFF
SD
SB
S9
S7
S5
S3
S0
+2
+1
Ts
-1
HEAT
Compressor-OFF
S0
S3
S5
S7
S9
SB
SD
SF
+1
Ts
-1
-2
Summary of Contents for MM-A0160HX
Page 1: ...Service Manual Air Conditioner Multi Split Type System Modular Multi System HFCR407C A90 0130 ...
Page 2: ......
Page 133: ...134 20 Additional Literature and Contacts ...
Page 134: ...135 20 Additional Literature and Contacts ...
Page 135: ...TOSHIBA AIR CONDITIONING www toshiba aircon co uk MADE IN UK A90 0130 Revised April 2001 ...