6
2
Operating Conditions
Summary
The units referred to within this manual conform with the protection requirements of
Directives 89/336/EEC Electromagnetic Compatibility and 73/23/EEC Low voltage.
Operating conditions of the unit are as follows:
Outdoor temperature
-5 ~ 43°C
Cooling
-15 ~ 21°C
Heating
Room Temperature
18 ~ 32°C
Cooling
15 ~ 29°C
Heating
Room humidity
<80%
Cooling
Note 1: Cooling capacity is rated at the following temperature conditions:
Indoor air inlet temperature
27°C DB, 19°C WB.
Outdoor air inlet temperature
35°C DB.
Note 2: Heating capacity is rated at the following temperature conditions:
Indoor air inlet temperature
20°C DB.
Outdoor air inlet temperature
7°C DB, 6°C WB.
Note 3: For details about the Outdoor unit, Indoor units or Remote Controller installation
refer to the relevant literature, i.e. Installation Instructions supplied with the units.
Note 4: Operatives handling refrigerants must be suitably qualified in accordance with local
and national codes of practice and statutory requirements.
Note 5: Legislation may regulate the removal of waste refrigerant from the systems. We advise
awareness of any regulations and duty of care. Waste refrigerant must NEVER be
discharged to atmosphere.
Note 6: Electrical work should be in accordance with all relevant codes of practice and should
be carried out by suitably qualified personnel.
Note 7: Metric/Imperial pipe conversion.
1 5/8
Note 8: Within this manual:
ODU
=
Outdoor Unit
IDU
=
Indoor Unit
R/C
=
Remote Controller
D.O.L. =
Direct On-Line compressor
INV
=
HP Inverter ODU
FIX
=
HP Fixed Speed ODU
DB
=
Dry Bulb
WB
=
Wet Bulb
Mg-Sw =
Magnetic Contactor
IOL
=
Inner Overload Relay
OCR
=
Over Current Relay
IGBT
=
Inverter Gate Bi-Polar Transistor
Note 9: MPaG
⇒
kgf/cm
2
G Conversion multiplier
10MPaG = 10.2kgf/cm
2
G
Diameter (mm)
6.4
9.5
12.7
15.9
19.0
22.0
28.6
34.9
41.3
54.1
Nominal diameter (inch)
1
⁄
4
3
⁄
8
1
⁄
2
5
⁄
8
3
⁄
4
7
⁄
8
1
1
⁄
8
1
3
⁄
8
1
5
⁄
8
2
1
⁄
8
Summary of Contents for MM-A0160HX
Page 1: ...Service Manual Air Conditioner Multi Split Type System Modular Multi System HFCR407C A90 0130 ...
Page 2: ......
Page 133: ...134 20 Additional Literature and Contacts ...
Page 134: ...135 20 Additional Literature and Contacts ...
Page 135: ...TOSHIBA AIR CONDITIONING www toshiba aircon co uk MADE IN UK A90 0130 Revised April 2001 ...