70
14
Troubleshooting
Diagnostic Procedure for Check Code
Is there a miswiring or
disconnection of PQ
communication cable
?
Is the connection
of CN101 on the indoor
P.C. board normal
?
Is the connection of
CN601 on the outdoor
interface P.C. board normal
?
Yes
No
No
Yes
No
Yes
No
Yes
Yes
No
Check communication cable.
Check wiring of wire connector.
Turn on source power of outdoor unit.
Clear the check code.
Is the power supply of the
outdoor unit turned on
?
Did a power failure occur
?
Yes
No
Check noise interference etc., and remove it.
Is there noise interference, etc.
?
Check indoor P.C. board.
If defective, replace.
Check code
Operation cause
1. Connection error of communication cable (PQ)
[95]
between indoor and outdoor units
Communication alarm between
2. Connection error of connector for indoor
indoor and outdoor
communication, P.C. board error
3. Connection error of connector for outdoor
communication, interface P.C. board error
NOTE:
1. When first turning on the power supply of the indoor unit, and when pushing the
START/STOP button before turning on the power supply of the outdoor unit, “95” may be
displayed. This is not abnormal therefore clear the check code.
2. If “95” is displayed only on the 7 segment of the outdoor unit, it is considered that power
supply of the master outdoor unit is not switched on, or a P.C. board error of the master
outdoor unit has occurred.
Summary of Contents for MM-A0160HX
Page 1: ...Service Manual Air Conditioner Multi Split Type System Modular Multi System HFCR407C A90 0130 ...
Page 2: ......
Page 133: ...134 20 Additional Literature and Contacts ...
Page 134: ...135 20 Additional Literature and Contacts ...
Page 135: ...TOSHIBA AIR CONDITIONING www toshiba aircon co uk MADE IN UK A90 0130 Revised April 2001 ...