Troubleshooting
Diagnostic Procedure for Check Code
84
14
Check code
Operation cause
1. Ps sensor error
2. Service valve closed
3. Indoor fan capacitor error
[bE]
4. Indoor/outdoor PMV blockage
Low-pressure protective operation
5. Indoor heat exchanger blockage
6. SV2 circuit
7. Incorrect wiring of communication cable between
indoor and outdoor units
Does the indoor fan operate
?
Is there a blockage on the
indoor filter or heat exchanger
?
Repair defective part.
Check indoor P.C. board.
If defective, replace.
Replace low-pressure sensor.
Clean or remove blockage.
No
Yes
No
Yes
Yes
Are the characteristics of
low-pressure sensor normal
?
No
Yes
Insufficient refrigerant,
blockage, pipe breakage.
(Check miswiring of the outdoor unit according to miswiring check function.)
Set normal wiring.
Is the wiring correct
?
No
Yes
Open valves fully.
Are the gas pipe and liquid
pipe service valves of the
outdoor unit fully open
?
Are the following
items related to indoor
fan motor normal
?
1. Connection
2. Capacitor
3. Motor
No
Yes
Modify SV2 bypass circuit.
Is SV2 bypass circuit normal
?
No
Yes
No