91
14
Troubleshooting
Diagnostic Procedure for Check Code
Check code
Operation cause
1. Power supply failure
[dA]
2. Outdoor fan error
Abnormal overheat of heat sink
3. Heat sink installation failure
4. Blockage of heat sink cooling duct
5. Defective inverter P.C. board
Is power supply voltage normal
?
Is the wiring connector
connection normal on the
inverter P.C. board
?
Check power supply.
Tighten screws.
Check the circuit wiring, for
example wiring to the inverter
compressor or connector connection.
No
Yes
No
Yes
Is there a screw loose on
the IGBT module or heat sink
on inverter P.C. board
?
Yes
No
Check inverter P.C. board.
Remove blockage.
Is there a blockage in the
heat sink cooling duct
?
Yes
No
Check fan and fan motor.
Is outdoor fan normal
?
No
Yes
Summary of Contents for MM-A0160HX
Page 1: ...Service Manual Air Conditioner Multi Split Type System Modular Multi System HFCR407C A90 0130 ...
Page 2: ......
Page 133: ...134 20 Additional Literature and Contacts ...
Page 134: ...135 20 Additional Literature and Contacts ...
Page 135: ...TOSHIBA AIR CONDITIONING www toshiba aircon co uk MADE IN UK A90 0130 Revised April 2001 ...