Troubleshooting
Diagnostic Procedure for Check Code
Check code
Operation cause
1. Leakage of PMV assembly on the liquid line
[dd]
2. Pd sensor/Ps sensor error
Outdoor refrigerant leakage
3. Blockage in SV2 valve circuit
detection
4. Blockage in SV3B valve circuit
5. Blockage in capillary of bypass between gas pipe
and heat exchanger line
Is there a blockage
in the PMV assembly on
the liquid line
?
Are the characteristics of
Pd sensor/Ps sensor output
voltage normal
?
Replace both the PMVs.
Replace SV2 valve.
Pd sensor/Ps sensor error.
Yes
No
No
Is there a blockage in the
capillary between the gas pipe
and the heat exchanger
liquid line
?
Replace capillary.
Yes
Yes
Is there a blockage
in SV2 valve circuit
?
Yes
No blockage
Check interface P.C. board.
Replace blocked part.
Is there a blockage
in SV3B valve circuit
?
Yes
No blockage
No blockage
Check connection
(SV2: CN312)
Is SV2 valve coil normally
connected
?
No
Yes