Troubleshooting
Diagnostic Procedure for Check Code
Check code
Operation cause
1. Inverter IOL operation
2. Service valve closed
[E5]
3. Cooling bypass PMV error
Inverter IOL operation
4. Miswiring of communication between indoor and
outdoor units
Is the IOL circuit normal
?
1.Connector
2.Wiring
3.Outdoor P.C. board
Is the cooling bypass PMV B
normal
?
Is wiring correct
?
Repair IOL circuit.
Cooling bypass PMV B error
Set normal wiring.
Open valves fully.
No
Yes
Are the gas pipe and liquid
pipe service valves of the
outdoor unit fully open
?
No
Yes
No
Yes
No
Yes
Insufficient refrigerant,
blockage, pipe breakage.
(Check miswiring of the outdoor unit according to miswiring check function.)