– 85 –
Check code
Location
of
detection
Description
System status
Error detection
condition(s)
Check items (locations)
H08
H08
01: TK1 sensor
error
02: TK2 sensor
error
03: TK3 sensor
error
04: TK4 sensor
error
05: TK5 sensor
error
I/F
Error in
temperature
sensor for oil level
detection
All stop
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TK1 sensor
connector.
• Check resistance characteristics of
TK1 sensor.
• Check for defect in outdoor P.C.
board (I/F).
All stop
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TK2 sensor
connector.
• Check resistance characteristics of
TK2 sensor.
• Check for defect in outdoor P.C.
board (I/F).
All stop
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TK3 sensor
connector.
• Check resistance characteristics of
TK3 sensor.
• Check for defect in outdoor P.C.
board (I/F).
All stop
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TK4 sensor
connector.
• Check resistance characteristics of
TK4 sensor.
• Check for defect in outdoor P.C.
board (I/F).
All stop
Sensor resistance is infinity
or zero (open / short circuit).
• Check connection of TK5 sensor
connector.
• Check resistance characteristics of
TK5 sensor.
• Check for defect in outdoor P.C.
board (I/F).
H14
H14
—
I/F
Compressor 2
case thermo
activation
All stop
Compressor 2 case thermo
was activated.
• Check Compressor 2 case thermo
circuit.
(Connector, Wiring, Circuit board)
• Open and check the service valve.
(Gas side, Liquid side)
• Check the outdoor PMV clogging
(PMV1, 2).
• Check the SV42 circuit.
• Check the SV4 circuit (SV41 / 42
miswiring).
• Check the opening status of indoor
PMV.
• Check the 4-way valve error.
• Check the refrigerant shortage.
H15
H15
—
I/F
TD2 sensor
miswiring
(incomplete
insertion)
All stop
Air discharge temperature of
(TD2) does not increase
despite compressor 2 being in
operation.
• Check installation of TD2 sensor.
• Check connection of TD2 sensor
connector and wiring.
• Check resistance characteristics of
TD2 sensor.
• Check for defect in outdoor P.C.
board (I/F).
Outdoor 7-segment display
Check
code
Sub-code
Main
remote
controller
Summary of Contents for MMC-AP0154H-E(-TR)
Page 145: ... 145 ...
Page 149: ... 149 9 2 1 Way cassette type SH 4 2 0 P A 8 1 0 P A 5 1 0 P A ...
Page 156: ... 156 MMU AP0056MH ...
Page 159: ... 159 9 4 Slim duct type MMD AP0054SPH AP0074SPH AP0094SPH AP0124SPH AP0154SPH AP0184SPH ...
Page 162: ... 162 MMD AP0056MH ...
Page 165: ... 165 9 5 Concealed duct standard type MMD AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 166: ... 166 ...
Page 169: ... 169 MMD AP0244BH AP0274BH AP0304BH AP0364BH AP0484BH ...
Page 170: ... 170 ...
Page 173: ... 173 MMD AP0564BH ...
Page 174: ... 174 ...
Page 177: ... 177 E Parts ...
Page 179: ... 179 9 6 Concealed duct high static pressure type MMD AP0184H AP0244H AP0274H AP0364H AP0484H ...
Page 183: ... 183 MMD AP0724H AP0964H ...
Page 184: ... 184 ...
Page 187: ... 187 9 7 Ceiling type MMC AP0154H AP0184H AP0244H AP0274H ...
Page 190: ... 190 MMC AP0364H AP0484H ...
Page 194: ... 194 9 8 Floor standing type MMF AP0154H AP0184H AP0244H AP0274H ...
Page 195: ... 195 MMF AP0154H AP0184H AP0244H AP0274H ...
Page 198: ... 198 MMF AP0364H AP0484H AP0564H ...
Page 199: ... 199 MMF AP0364H AP0484H AP0564H ...
Page 203: ... 203 9 9 Floor standing concealed type MML AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 206: ... 206 MML AP0244BH ...
Page 209: ... 209 9 10 Floor standing cabinet type MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 210: ... 210 MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 213: ... 213 MML AP0244H ...
Page 214: ... 214 MML AP0244H ...