Check code
Location
of
detection
Description
System status
Error detection
condition(s)
Check items (locations)
Outdoor 7-segment display
Check
code
Sub-code
Main
remote
controller
P03
—
P03
I/F
Discharge
temperature TD1
error
All stop
Discharge temperature (TD1)
exceeds 115 ˚C.
• Check outdoor service valves (gas
side, liquid side) to confirm full
opening.
• Check outdoor PMVs (PMV1, 2, 4)
for clogging.
• Check resistance characteristics of
TD1 sensor.
• Check for insufficiency in
refrigerant quantity.
• Check for defect in 4-way valve.
• Check for leakage of SV4 circuit.
• Check SV4 circuit (wiring or
installation error in SV41, SV42 or
SV43).
P04
01: Compressor
1 side
02: Compressor
2 side
03: Compressor
3 side
P04
IPDU
Activation of high-
pressure SW
All stop
High-pressure SW is activated. • Check connection of highpressure
SW connector.
• Check for defect in Pd pressure
sensor.
• Check outdoor service valves (gas
side, liquid side) to confirm full
opening.
• Check for defect in outdoor fan.
• Check for defect in outdoor fan
motor.
• Check outdoor PMVs (PMV1, 2) for
clogging.
• Check indoor / outdoor heat
exchangers for clogging.
• Check for short-circuiting of
outdoor suction / discharge air
flows.
• Check SV2 circuit for clogging.
• Check for defect in outdoor P.C.
board (I/F).
• Check for error in indoor fan system
(possible cause of air flow
reduction).
• Check opening status of indoor
PMV.
• Check indoor-outdoor
communication line for wiring error.
• Check for faulty operation of check
valve in discharge pipe convergent
section.
• Check gas balancing SV4 valve
circuit.
• Check SV5 valve circuit.
• Check for refrigerant overcharging.
P05
SMMS (Series 1)
01: Open phase
detected
02: Phase
sequence error
P05
I/F
Open phase
detected, Phase
sequence error
All stop
• Phase sequence error was
detected when the power is
turned on.
• Open phase error was
detected when the power is
turned on.
• Check the phase sequence of
outdoor power wiring.
• Check the outdoor PC board (I/F)
error.
P07
01: Compressor
1 side
02: Compressor
2 side
03: Compressor
3 side
P07
IPDU
I/F
Heat sink
overheating error
All stop
Temperature sensor built into
IGBT (TH) is overheated.
• Check power supply voltage.
• Check outdoor fan system error.
• Check heat sink cooling duct for
clogging.
• Check IGBT and heat sink for
thermal performance for faulty
installation.
(e.g. mounting screws and thermal
conductivity)
• Check for defect in A3-IPDU.
(faulty IGBT built-in temperature
sensor (TH))
P10
Detected indoor
address
P10
Indoor unit Indoor overflow
error
All stop
• Float switch operates.
• Float switch circuit is open-
circuited or disconnected at
connector.
• Check float switch connector.
• Check operation of drain pump.
• Check drain pump circuit.
• Check drain pipe for clogging.
• Check for defect in indoor P.C.
board.
MG-CTT: Magnet contactor
SMMS-i
(Series 4)
00:
I/F
Detection of open
phase / phase
sequence
01: Compressor
1 side
02: Compressor
2 side
03: Compressor
3 side
Inverter DC
voltage (Vdc) error
(compressor)
MG-CTT error
All stop
• Open phase is detected
when power is turned on.
• Inverter DC voltage is too
high (overvoltage) or too low
(undervoltage).
• Check for defect in outdoor P.C.
board (I/F).
Summary of Contents for MMC-AP0154H-E(-TR)
Page 145: ... 145 ...
Page 149: ... 149 9 2 1 Way cassette type SH 4 2 0 P A 8 1 0 P A 5 1 0 P A ...
Page 156: ... 156 MMU AP0056MH ...
Page 159: ... 159 9 4 Slim duct type MMD AP0054SPH AP0074SPH AP0094SPH AP0124SPH AP0154SPH AP0184SPH ...
Page 162: ... 162 MMD AP0056MH ...
Page 165: ... 165 9 5 Concealed duct standard type MMD AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 166: ... 166 ...
Page 169: ... 169 MMD AP0244BH AP0274BH AP0304BH AP0364BH AP0484BH ...
Page 170: ... 170 ...
Page 173: ... 173 MMD AP0564BH ...
Page 174: ... 174 ...
Page 177: ... 177 E Parts ...
Page 179: ... 179 9 6 Concealed duct high static pressure type MMD AP0184H AP0244H AP0274H AP0364H AP0484H ...
Page 183: ... 183 MMD AP0724H AP0964H ...
Page 184: ... 184 ...
Page 187: ... 187 9 7 Ceiling type MMC AP0154H AP0184H AP0244H AP0274H ...
Page 190: ... 190 MMC AP0364H AP0484H ...
Page 194: ... 194 9 8 Floor standing type MMF AP0154H AP0184H AP0244H AP0274H ...
Page 195: ... 195 MMF AP0154H AP0184H AP0244H AP0274H ...
Page 198: ... 198 MMF AP0364H AP0484H AP0564H ...
Page 199: ... 199 MMF AP0364H AP0484H AP0564H ...
Page 203: ... 203 9 9 Floor standing concealed type MML AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 206: ... 206 MML AP0244BH ...
Page 209: ... 209 9 10 Floor standing cabinet type MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 210: ... 210 MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 213: ... 213 MML AP0244H ...
Page 214: ... 214 MML AP0244H ...