– 97 –
Procedure 1: reading setting data from EEPROM
(Read the setting data from EEPROM, including both the factory settings and any modifications made to them on
site.)
1
Push the
+
+
buttons simultaneously and hold for at least 4 seconds. (This number
corresponds to the same number shown on the Remote Controller Operation Diagram.)
* In the case of group control, the unit No. displayed first is the indoor unit No. of the header unit.
At the same time, the CODE No. (DN code) 10 is displayed, and the fan of the selected indoor unit comes
on, with the louver swinging, depending on the model.
2
Each time the
button is pushed, one of the indoor unit No. under group control is
displayed in turn.
* The fan of the selected indoor unit comes on, with the louvers swinging, depending on the model.
3
The
button allows you to move the CODE No. (DN code) up / down by one place.
4
First, change the CODE No. (DN code) from 10 to 01. (To set filter sign lighting time)
Jot down the setting data displayed.
5
Change the CODE No. (DN code) using the
button.
Again, jot down the setting data displayed.
6
Repeat step
5
until all the setting data has been jotted down. (See the CODE No. list.)
* CODE No. (DN code) go from 01 to FF with a few gaps along the way.
7
When finished, push the
button to bring the system back to normal off state.
(It takes the system about 1 minute to become responsive to remote controller operation.)
CODE No. (DN code) necessary at minimum
The type and capacity of the indoor unit are necessary for fan speed setting.
DN
Contents
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor address
14
Group address
Remote controller operation diagram
Summary of Contents for MMC-AP0154H-E(-TR)
Page 145: ... 145 ...
Page 149: ... 149 9 2 1 Way cassette type SH 4 2 0 P A 8 1 0 P A 5 1 0 P A ...
Page 156: ... 156 MMU AP0056MH ...
Page 159: ... 159 9 4 Slim duct type MMD AP0054SPH AP0074SPH AP0094SPH AP0124SPH AP0154SPH AP0184SPH ...
Page 162: ... 162 MMD AP0056MH ...
Page 165: ... 165 9 5 Concealed duct standard type MMD AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 166: ... 166 ...
Page 169: ... 169 MMD AP0244BH AP0274BH AP0304BH AP0364BH AP0484BH ...
Page 170: ... 170 ...
Page 173: ... 173 MMD AP0564BH ...
Page 174: ... 174 ...
Page 177: ... 177 E Parts ...
Page 179: ... 179 9 6 Concealed duct high static pressure type MMD AP0184H AP0244H AP0274H AP0364H AP0484H ...
Page 183: ... 183 MMD AP0724H AP0964H ...
Page 184: ... 184 ...
Page 187: ... 187 9 7 Ceiling type MMC AP0154H AP0184H AP0244H AP0274H ...
Page 190: ... 190 MMC AP0364H AP0484H ...
Page 194: ... 194 9 8 Floor standing type MMF AP0154H AP0184H AP0244H AP0274H ...
Page 195: ... 195 MMF AP0154H AP0184H AP0244H AP0274H ...
Page 198: ... 198 MMF AP0364H AP0484H AP0564H ...
Page 199: ... 199 MMF AP0364H AP0484H AP0564H ...
Page 203: ... 203 9 9 Floor standing concealed type MML AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 206: ... 206 MML AP0244BH ...
Page 209: ... 209 9 10 Floor standing cabinet type MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 210: ... 210 MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 213: ... 213 MML AP0244H ...
Page 214: ... 214 MML AP0244H ...