Check method

On the wired remote controller, central control remote controller and the interface P.C. board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. board) to display the operation 
is provided. Therefore the operation status can be known. Using this self-diagnosis function, a trouble or position with error of the air conditioner can be found as shown in the following table.

Check code list

The following list shows each check code. Find the check contents from the list according to part to be checked.
• In case of check from indoor remote controller: See “Wired remote controller display” in the list.
• In case of check from outdoor unit: See “Outdoor unit 7-segment display” in the list.
• In case of check from AI-NET central control remote controller: See “AI-NET central control display” in the list.
• In case of check from indoor unit with a wireless remote controller: See “Sensor block display of receiving unit” in the list.

: Lighting,  : Flashing,  : Goes off

AI-NET: Artificial Intelligence

IPDU: Intelligent Power Drive Unit

ALT: Flashing is alternately when there are two flashing LED.

SIM: Simultaneous flashing when there are two flashing LED.

Check code

Wireless remote controller

Check code name

Judging device

Wired remote 

controller display

Outdoor unit 7-segment display

AI-NET central 

control display

Sensor block display of receiving unit

Auxiliary code

Operation

Timer

Ready

Flash

E01

Communication error between indoor unit and remote controller (Detected at 

remote controller side)

Remote controller

E02

Remote controller transmission error

Remote controller

E03

97

Communication error between indoor unit and remote controller (Detected at 

indoor unit side)

Indoor unit

E04

04

Communication circuit error between indoor / outdoor unit (Detected at indoor 

unit side)

Indoor unit

E06

E06

No. of indoor units in which sensor has been 

normally received

04

Decrease of No. of indoor units

I/F

E07

Communication circuit error between indoor / outdoor unit (Detected at 

outdoor unit side)

I/F

E08

E08

Duplicated indoor unit addresses

96

Duplicated indoor unit addresses

Indoor unit • I/F

E09

99

Duplicated master remote controllers

Remote controller

E10

CF

Communication error between indoor unit MC

Indoor unit

E12

E12

01:Indoor / Outdoor units communication
02:Outdoor / Outdoor units communication

42

Automatic address start error

I/F

E15

E15

42

No indoor unit during automatic addressing

I/F

E16

E16

00:Capacity over
01 ~:No. of connected units

89

Capacity over / No. of connected indoor units

I/F

E18

97, 99

Communication error between header and follower units Indoor unit

Indoor unit

E19

E19

00:No header
02:Two or more header units

96

Outdoor header units quantity error

I/F

E20

E20

01:Outdoor unit of other line connected
02:Indoor unit of other line connected

42

Other line connected during automatic address

I/F

E21

E21

02:No header unit
00:Multiple number of header units

42

Error in number of heat storage master units

I/F

E22

E22

42

Reduction in number of heat storage units

I/F

E23

E23

15

Sending error in communication between outdoor units
Error in number of heat storage units (trouble with reception)

I/F

E25

E25

15

Duplicated follower outdoor addresses

I/F

E26

E26

No. of outdoor units which received signal 

normally

15

Decrease of No. of connected outdoor units

I/F

E28

E28

Detected outdoor unit number

d2

Follower outdoor unit error

I/F

E31

E31

Number of IPDU (*1)

CF

IPDU communication error

I/F

31-EN

32-EN

+00EH99880501_01EN.book  Page 16  Thursday, April 7, 2011  10:15 AM

Summary of Contents for MMC-AP0154H-TR

Page 1: ...4H E MMF AP0484H E MMF AP0564H E Indoor Unit Model name Floor Standing Type MMF AP0154H E MMF AP0184H E MMF AP0244H E MMF AP0274H E AIR CONDITIONER MULTI TYPE Installation Manual 00EH99880501_01EN book Page 1 Thursday April 7 2011 10 15 AM ...

Page 2: ...ved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters ...

Page 3: ...cap Repair of outdoor unit Gloves to provide protection for electricians and from heat Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts You might ge...

Page 4: ...acking carton You may injure yourself if the bands should break Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Installation Install the air conditioner securely in a location where the base can sustain the weight adequately If the strength is not enough the unit may fall down resulting in inju...

Page 5: ...act a qualified service person 1 to have the repairs done Do not set the circuit breaker to the ON position until the repairs are completed Relocation Only a qualified installer 1 or qualified service person 1 is allowed to relocate the air conditioner It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire electric shocks injury water leakage noise and or...

Page 6: ... the plastic parts to be damaged and other such problems to result Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be disrupted a disruption of the air flow may cause the air conditioner s performance to deteriorate or the unit to shut down Locations where an in house power generator is used for the power supply The power line freq...

Page 7: ...or immediately for safety Installation of indoor unit Fixing to the wall surface Use the attached wall fixing bracket by inverting it at upper side of the unit Fix the indoor unit to the wall surface using the attached screw bolts anchor bolts or etc at two positions A many holes for fixing the indoor unit to wall surface and for fixing the indoor unit itself are provided on the bracket Sliding th...

Page 8: ... room Air intake grille Bracket for fixing to floor Bracket for fixing to wall Electrical control box cover Vertical louver Turn the vertical louver while lifting up lightly and then insert it into the clearance of extrusion of the coupling rod Extrusion Coupling rod 8 m or less 5 Drain Piping CAUTION Following the Installation Manual perform the drain piping work so that water is properly drained...

Page 9: ...5 mm or more on AP015 to AP027 model If the clearance is less than 5 mm drip proof cover cannot be removed and the electrical control box cannot be took out Drain hose Drain pan Heat insulator Hart polyvinyl chloride pipe Adhesion for hart polyvinyl chloride pipe used To connect drain hose on right route it through the knock out for refrigerant piping on AP015 to AP027 model Power supply wire take...

Page 10: ...12 7 16 6 15 9 19 7 Use two wrenches to connect the indoor unit pipe Use the tightening torque levels as listed in the following table Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorr...

Page 11: ...the power supply specifications follow to the following table If capacity is little it is dangerous because overheat or burnout may be caused For specifications of the power capacity of the outdoor unit and the power supply wires refer to the Installation Manual attached to the outdoor unit Indoor unit power supply For the power supply of the indoor unit prepare the exclusive power supply separate...

Page 12: ...gh voltage circuit How to remove the electrical control box cover AP015 to AP027 models Take off screws 1 and 2 at this side of the electrical control box and remove the drip proof cover Take off screws 3 and 4 at front side of the electrical control box and remove the electrical control box cover AP036 to AP056 models Take off screws 3 and 4 at front side of the electrical control box and remove ...

Page 13: ...on is pushed While air conditioners are operated under the group control ALL is displayed first When is pushed the indoor unit number displayed following ALL is the header unit 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the indoor unit to change settings for The fan of the selected u...

Page 14: ...s been performed using this method do NOT forget to release the shorting of CN72 after the test run is completed Operate the unit with the wired remote controller as usual For the procedure of the operation refer to the attached Owner s Manual to the outdoor unit A forced test run can be executed in the following procedure even if the operation stops by thermostat OFF In order to prevent a serial ...

Page 15: ...nd outdoor units regularly will result in poor performance freezing water leakage and even compressor failure 4 1 3 Inspection before maintenance Following inspection must be carried out by a qualified installer or qualified service person Maintenance List Parts Inspection method Heat exchanger Access from inspection opening and remove the access panel Examine the heat exchanger if there is any cl...

Page 16: ...rs The log can be confirmed from both operating status and stop status 1 When and buttons are pushed simultaneously for 4 seconds or more the following display appears If is displayed the mode enters in the error log mode 01 Order of error log is displayed in CODE No Error code is displayed in CHECK Indoor unit address in which an error occurred is displayed in Unit No 2 Every pushing of button us...

Page 17: ...roller E03 97 Communication error between indoor unit and remote controller Detected at indoor unit side Indoor unit E04 04 Communication circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received 04 Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit Detected at...

Page 18: ... 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side 1d Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side 17 Current detect circuit system error IPDU H04 H04 44 Comp 1 case thermo operation I F H05 H05 TD1 sensor miswiring I F H06 H06 20 Low pressure protective operation I F H07 H07 d7 Oil level down detective protection I F H08 H08 01 TK1 sensor error 02 TK2 sensor error ...

Page 19: ... side 03 Comp 3 side AF ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC voltage error comp I F P07 P07 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side IC ALT Heat sink overheat error IPDU I F P09 P09 Detected heat storage address 47 ALT No heat storage unit water error Heat storage unit P10 P10 Detected indoor unit address ...

Page 20: ...mp 2 Comp 3 Fan Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display AI NET central control display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash C05 Sending error in TCC LINK central control device TCC LINK C06 Receiving error in TCC LINK central control device TCC LINK C12 Batch a...

Page 21: ...r Nick Ball Toshiba EMEA Engineering Director Toshiba Carrier UK Ltd Porsham Close Belliver Industrial Estate PLYMOUTH Devon PL6 7DB United Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMF AP0154H E MMF AP0184H E MMF AP0244H E MMF AP0274H E MMF AP0364H E MMF AP0484H E MMF AP0564H E Commercial name Super Modular Multi System Air Conditio...

Page 22: ...ulti air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE 2 The stand...

Page 23: ...nd fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE NO 01 F NO CHANGE F NONE 0000 F 150H 0001 F 2500H 0002 F 5000H 0003 F 10000H 0004 Filter sign lighting time CODE NO 01 F NO CHANGE F NONE 0000 F 150H 0001 F 2500H 0002 F 5000H 0003 F 10000H 0004 Filter sign lighting time CODE NO 01 F NO CHANGE F NONE 0000 F...

Page 24: ...EH99880599 00EH99880501_01EN book Page 23 Thursday April 7 2011 10 15 AM ...

Reviews: