Duplicated indoor units with priority (Displayed in indoor unit with priority)
I/F
L06
L06
No. of indoor units with priority
96
SIM
Duplicated indoor units with priority (Displayed in unit other than indoor unit
with priority)
I/F
L07
—
—
99
SIM
Group line in individual indoor unit
Indoor unit
L08
L08
—
99
SIM
Indoor unit group / Address unset
Indoor unit, I/F
L09
—
—
46
SIM
Indoor unit capacity unset
Indoor unit
L10
L10
—
88
SIM
Outdoor unit capacity unset
I/F
L17
—
—
46
SIM
Outdoor unit type mismatch error
I/F
L20
—
—
98
SIM
Duplicated central control addresses
AI-NET, Indoor unit
L26
L26
Number of heat storage units connected
46
SIM
Too many heat storage units connected
I/F
L27
L27
Number of heat storage units connected
46
SIM
Error in number of heat storage units connected
I/F
L28
L28
—
46
SIM
Too many outdoor units connected
I/F
L29
L29
Number of IPDU (*1)
CF
SIM
No. of IPDU error
I/F
L30
L30
Detected indoor unit address
b6
SIM
Indoor unit outside interlock
Indoor unit
—
L31
—
—
—
Extended I/C error
I/F
P01
—
—
11
ALT
Indoor fan motor error
Indoor unit
P03
P03
—
1E
ALT
Discharge temp. TD1 error
I/F
P04
P04
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
21
ALT
High-pressure SW system operation
IPDU
P05
P05
00:
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
AF
ALT
Phase missing detection / Power failure detection
Inverter DC voltage error (comp.)
Inverter DC voltage error (comp.)
Inverter DC voltage error (comp.)
I/F
P07
P07
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
IC
ALT
Heat sink overheat error
IPDU, I/F
P09
P09
Detected heat storage address
47
ALT
No heat storage unit water error
Heat storage unit
P10
P10
Detected indoor unit address
Ob
ALT
Indoor unit overflow error
Indoor unit
P12
—
—
11
ALT
Indoor unit fan motor error
Indoor unit
P13
P13
—
47
ALT
Outdoor liquid back detection error
I/F
P15
P15
01:TS condition
02:TD condition
AE
ALT
Gas leak detection
I/F
P17
P17
—
bb
ALT
Discharge temp. TD2 error
I/F
P18
P18
—
E2
ALT
Discharge temp. TD3 error
I/F
P19
P19
Detected outdoor unit number
O8
ALT
4-way valve inverse error
I/F
P20
P20
—
22
ALT
High-pressure protective operation
I/F
P22
P22
0*:IGBT circuit
1*:Position detective circuit error
3*:Motor lock error
4*:Motor current detection
C*:TH sensor error
D*:TH sensor error
E*:Inverter DC voltage error (outdoor unit
fan)
1A
ALT
Outdoor unit fan IPDU error
Note: Ignore 0 to F displayed in “*” position.
IPDU
P26
P26
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
14
ALT
G-TR short protection error
IPDU
Check code
Wireless remote controller
Check code name
Judging device
Wired remote
controller display
Outdoor unit 7-segment display
AI-NET central
control display
Sensor block display of receiving unit
Auxiliary code
Operation
Timer
Ready
Flash
35-EN