– 98 –
FILE NO. SVM-13085
No. Part name
Procedure
Remarks
Heat
exchanger
1. Detachment
1) Recover the refrigerant gas and then
remove the refrigerant pipe of the
indoor unit.
2) Perform works of 1 of .
Pull out sensor wires from the holder.
3) The screw that is the fixing of the piping
support is removed, and the piping
support is removed. (Ø4 x 10, 2 pcs.)
4) The screw of the partition plate is
removed while holding the heat
exchanger, the partition plate is removed.
(Ø4 x 10, 4 pcs.)
5) The screw of the heat exchanger on the
partition plate and the other side is
removed while holding the heat exchanger,
and the heat exchanger is removed.
2. Attachment
1) Attach as before in heat exchanger
䊻㻌
sensor
䊻
piping support
䊻
drain pan
䊻
under panel order.
2) Connect the refrigerant pipe as original, and
then perform vacuuming.
9
11
Screws
Screws
Fixing plate
Screws
SVM-13085.indb 98
SVM-13085.indb 98
12/24/13 10:56 AM
12/24/13 10:56 AM