– 96 –
FILE NO. SVM-
16042
No.
Part name
Procedure
Remarks
Drain pan
1. Detachment
1) Perform works of 1 of
1
, 1 of
7
and
1 of
8
.
2) Remove the drain cap and then extract
the drain water accumulated in the
drain pan.
NOTE
When removing the drain cap, be sure to
receive drain water using a bucket, etc.
3) The drain hose is removed from the
drain pan joint while picking up the
hose band.
4) The heat insulator stuck on air discharge
side of the drain pan is peeled off and
an inside shoulder screw is removed.
AP015 to AP027 type : (1 pc.)
AP036 to AP056 type : (2 pcs.)
* When installing, the heat insulator
peeled off is used.
5) Slide to the air discharge side, remove
the drain pan.
2. Attachment
1) The drain cap is surely inserted up to
the drain pan root.
2) Slide to the air discharge side, hooking
surely the frame on fan side.
3) Attach the shoulder screws as original
position, the heat insulator is stuck on.
4) The hose band is used and the drain
hose is installed.
Drain cap
Heat insulator
Shoulder screw
9