3-102
(2) Outdoor unit information data display (Displayed on each outdoor unit)
SW03 SW02 SW01
Displayed content
A
[U1] to [U5] : Outdoor unit number (1 : Inverter)
B
[– –] : Normal time (No error),
a check code is displayed in abnormality.
1
1
1
Check code
<SW04>
Push function :
Only fan of unit in which an error occurred operates.
<SW04 + SW05> Push function : Only fan of normal unit operates.
<SW05>
Push function : Fan operation function is interrupted.
A
[U1] to [U2] : Outdoor unit number
2
Type of installed
compressor
B
[ A] : Fixed-speed 2 in 1, [ b] : Fixed-speed 2 compressor
[ C] : Fixed-speed single, [ d] : Inverter (2 in 1)
A
—
3
Operation mode
B
[ C] : Cooling operation, [H]: Heating operation, [J] : Defrost operation
A
[ 6], [ 8], [10] : 6, 8, 10 HP
4
Outdoor unit capacity
B
[HP]
A
[1. –] : No.1 compressor stop status, [1. 1] : During operation
For inverter, the frequency code is displayed : [00] to [FF]
B
[2. –] : No.2 compressor stop status, [2. 1] : During operation
5
Compressor operation
command
<SW04>
Push function :
IPDU frequency data is displayed in decimal notation.
<SW05>
Push function :
Release of frequency data display in decimal notation
A
[FP]
6
Outdoor fan operation
pattern
B
[ 0] to [16] : 0 wave (stop) to 16 waves (All waves)
A
[C1] : Under No.1 compressor backup set up
7
Compressor backup
B
[C2] : Under No.2 compressor backup set up
A
—
8
—
B
—
A
B
4-way valve : ON / SV2 : OFF
H. 1
2. 0
9
4-way valve : OFF / SV2 : ON
H. 0
2. 1
SV3A : ON / SV3B : OFF / SV3C : OFF
3. 1
0. 0
SV3A : OFF / SV3B : ON / SV3C : OFF
3. 0
1. 0
10
SV3A : OFF / SV3B : OFF / SV3C : ON
3. 0
0. 1
SV41 : ON / SV42 : OFF
4.
1. 0
11
SV41 : OFF / SV42 : ON
4.
0. 1
12
—
—
—
13
Control valve output
—
—
—
14
PMV 1 + PMV 2 opening [ 00] to [A00] : 0 to 1000 pulse
0
0 P
15
PMV B opening
[ 00] to [500] : 0 to 500 pulse
0
0 P
A
[OL]
B
[ ] : Initial display, [FF] : Oil judgment start status
[A0] : Adequate, [A1] : Shortage, [A2 to A4] : Detection error
16
Oil level judgment status
<SW04>
Push function :
Oil level judgment control forcible start
(Detection starts after timer count down)
<SW05>
Push function :
Oil level shortage status/Continuous counter display
(Displayed for several seconds)
NOTE : The push-switch function operates by input from the inverter unit.