3-103
(3) Outdoor cycle data display (Displayed on each outdoor unit)
SW03 SW02 SW01
Displayed content
A
B
1
Pd pressure sensor
H
*
*
*
2
Ps pressure sensor
Pressure sensor data is displayed with (MPaG).
L
*
*
*
Symbol
t d
1
3
TD1 temp. sensor
Data
*
*
*
Symbol
t d
2
4
TD2 temp. sensor
Data
*
*
*
Symbol
t s
5
TS temp. sensor
Data
*
*
*
Symbol
t E
1
6
TE1 temp. sensor
Data
*
*
*
7
—
Symbol
F 1
8
TK1 temp. sensor
Data
*
*
*
Symbol
F 2
9
TK2 temp. sensor
Data
*
*
*
Symbol
F 3
2
10
1
TK3 temp. sensor
Temp. sensor data is displayed with (°C).
• Symbol display and data display are
alternately exchanged every several
seconds.
• Data is displayed in the part marked with
[
*
].
• If data is negative data, [–
*
*
*
] is
displayed.
Data
*
*
*
(4) Outdoor cycle data display (Displayed on inverter unit)
*
Outdoor cycle data display is used when the fixed-speed unit information is displayed on the 7 segment
section of the inverter unit.
SW03 SW02 SW01
Displayed content
1 to 4
3
A [U2] to [U5] : Outdoor unit number (Set up with SW03)
1
Check code
B [– –] : Normal time (No trouble), a check code is displayed in abnormality.
A [U2] to [U5] : Outdoor unit number (Set up with SW03)
2
Type of fixed-speed
compressor
B [ A] : Fixed-speed 2 in 1 compressor
[ b] : Fixed-speed 2 compressor
[ C] : Fixed-speed single compressor
A [U2] to [U5] : Outdoor unit number (Set up with SW03)
3
Fixed-speed unit
capacity
B [ 6], [ 8], [10] : 6, 8, 10HP
A [U2] to [U5] : Outdoor unit number (Set up with SW03)
4
Fixed-speed
compressor operation
command
B [10] : No.1 compressor start/No.2 compressor stop status
[01] : No.1 compressor stop/No.2 compressor start status
A [U2] to [U5] : Outdoor unit number (Set up with SW03)
5
—
B
—
A [U2] to [U5] : Outdoor unit number (Set up with SW03)
6
—
B
—
A [U2] to [U5] : Outdoor unit number (Set up with SW03)
7
Oil level judgment
status
B [ ] : Normal time, [ L] : Shortage
NOTE : The outdoor unit number is set by selecting SW03.
SW03
Outdoor unit number
7 segment display A
1
Outdoor No.2 unit (Fixed-speed 1)
[U2]
2
Outdoor No.3 unit (Fixed-speed 2)
[U3]
3
Outdoor No.4 unit (Fixed-speed 3)
[U4]
4
Outdoor No.5 unit (Fixed-speed 4)
[U5]