3-113
PMV opening
Normal operation
Full open
Full close
Medium opening (Medium degree of full open and full close)
CN33
CN32
Open
Open
Open
Short
Short
Open
Short
Short
3-7-1-6. Indoor PMV full open/full close function
PMV used in the indoor unit can be forcibly opened fully, closed fully, and opened in medium degree for 2 minutes.
[4-way Air Discharge Cassette type]
3-7-1-7. Switch positions at shipment from the factory
SW No.
Function
Description
Position at
shipment from factory
SW01
Indoor unit
No. set up
Group operation control set up
1 : Master unit
2 to 16 Server units
ON
Address set up by remote
controller is unavailable.
No. 7
OFF
Address set up by remote
controller is available.
SW02
Network
address set
up
For contents of address set up, see the next page.
No. 1
ON
Normal
No. 2
OFF
Normal
SW03
(
*
)
No. 1
OFF
Normal
No. 2
OFF
Normal
SW05
(
*
)
SW08
Indoor horse
power set up
Set up at shipment from factory
For contents of set up, see the next page.
SW06
Ceiling height
select set up
When height of ceiling exceeds 2.7m, set No.1 to
ON side.
ON
Impossible to communication
(Non relay)
No. 1
OFF
(Normal) possible to
communication
No. 2
OFF
Normal
SW07
Central
control
switching
1
ON
1
2
3
4
5
6
7
ON
1
2
ON
1
2
ON
1
2
3
4
ON
1
2
ON
1
2
REFERENCE :
*
marked switches are not used for intelligent variable refrigerant system air conditioner.