1-46
Model name
MML-
P0091BH
P0151BH
P0181BH
P0241BH
Cooling/Heating capacity (Note 1)
(kW)
2.8/3.2
4.5/5.0
5.6/6.3
7.1/8.0
Power supply
1 phase 60Hz 220V (Power exclusive for indoor is required.)
Running current
(A)
0.27
0.46
0.46
0.51
Power consumption
(kW)
0.058
0.096
0.09
0.110
Power factor
(%)
98
95
95
98
Electrical
characteristics
Starting current
(A)
0.6
0.8
0.8
1.0
Appearance
Zinc hot dipping steel plate
Outer dimension
Height x Width x
Depth
(mm)
600 x 745 x 220
600 x 1,045 x 220
Total weight
(kg)
21
29
Heat exchanger
Finned tube
Soundproof/Heat-insulating material
Non-flammable insulation
Fan
Centrifugal fan
Standard air flow
(High/Mid./Low)
(m³/h)
460
740
950
Motor
(W)
19
70
Fan unit
Static pressure
range
(kPa)
0
Air filter
Attached
Controller
Remote controller (Part sold separately)
Gas side
(mm)
Ø12.7
Ø15.9
Liquid side
(mm)
Ø6.4
Ø9.5
Connecting pipe
Drain port (Nominal dia.)
20 (One side of male screw)
Sound level (Note 2) (High/Mid./Low)
(dB•A)
36 (34/32)
42 (37/33)
• Floor Standing Concealed Type (TENTATIVE)
60Hz
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based on the
reference piping. The reference piping consists of 3 m of main piping and 2 m of branch piping connected with 0 meter height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note
: Rated conditions
Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB