1-4
Modular Multi System Outdoor Unit :
List of Product and Combined Model Name
1. Allocation standard of model name
HP
(Capacity
code)
Model
name
MMY-
No. of
combined
units
Inverter
8HP
MMY-
Used
Q'ty
Inverter
10HP
MMY-
Used
Q'ty
Fixed-speed
6HP
MMY-
Used
Q'ty
Fixed-speed
8HP
MMY-
Used
Q'ty
Fixed-speed
10HP
MMY-
Used
Q'ty
8HP ( 8) MP0801T8
1
MP0801T8
1
10HP (10) MP1001T8
1
MP1001T8
1
14HP (14)
P1401T8
2
MP0801T8
1
MP06018
1
16HP (16)
P1601T8
2
MP0801T8
1
MP08018
1
18HP (18)
P1801T8
2
MP1001T8
1
MP08018
1
20HP (20)
P2001T8
2
MP1001T8
1
MP10018
1
22HP (22)
P2201T8
3
MP0801T8
1
MP06018
1
MP08018
1
24HP (24)
P2401T8
3
MP0801T8
1
MP08018
2
26HP (26)
P2601T8
3
MP1001T8
1
MP08018
2
28HP (28)
P2801T8
3
MP1001T8
1
MP08018
1
MP10018
1
30HP (30)
P3001T8
3
MP1001T8
1
MP10018
2
32HP (32)
P3201T8
4
MP0801T8
1
MP08018
3
34HP (34)
P3401T8
4
MP1001T8
1
MP08018
3
36HP (36)
P3601T8
4
MP1001T8
1
MP08018
2
MP10018
1
38HP (38)
P3801T8
4
MP1001T8
1
MP08018
1
MP10018
2
40HP (40)
P4001T8
4
MP1001T8
1
MP10018
3
42HP (42)
P4201T8
5
MP1001T8
1
MP08018
4
44HP (44)
P4401T8
5
MP1001T8
1
MP08018
3
MP10018
1
46HP (46)
P4601T8
5
MP1001T8
1
MP08018
2
MP10018
2
Cooling Only model
2. Range of combined capacity
No. of combined units: 1 to 5 units
Capacity of combined units : 14 HP (140 type) to 46 HP (460 type)
3. Restriction for combination of units
(1) The inverter unit should have the maximum capacity among all units in that combination.
(2) The fixed-speed unit 6HP is available only with the combination of 14 HP and 22 HP.
(It cannot be used for other combination.)
4. Rated conditions (Rated mode : Condition)
Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
MMY– M
P
T
8
Power supply specifications, 3Ø 380–415 V, 50Hz ....... 8
T : Capacity variable unit, No mark : Fixed speed unit
Development series No.
Capacity rank HP x 10
New refrigerant R407C
M : Single module unit, No mark : Combined Model name
Modular Multi
50Hz