1-66
Equivalent HP
Equivalent to 46HP
Set Model name
Heat Pump
MMY-
P4601HT7
Outdoor unit type
Inverter
Fixed
speed type
Fixed
speed type
Fixed
speed type
Fixed
speed type
Cooling Only
MMY-
MP1001T7
MP10017
MP10017
MP08017
MP08017
Outdoor unit model
Heat Pump
MMY-
MP1001HT7
MP1001H7
MP1001H7
MP0801H7
MP0801H7
Rated cooling capacity (
*
1)
(kW)
128.8
Standard heating capacity (
*
1)
(kW)
150.5
Power supply (
*
2)
3 phase 60Hz 380V
Running current
(A)
97.9
Power consumption
(kW)
57.7
Power factor
(%)
85
EER (kW/kW)
(Energy Efficiency Ratio)
2.23
Starting current
(A)
21.4
Cooling
Instantaneous
maximum current
(A)
205
Running current
(A)
97.1
Power consumption
(kW)
57.3
Power factor
(%)
85
EER (kW/kW)
(Energy Efficiency Ratio)
2.63
Starting current
(A)
21.1
Electrical
characteristics
(
*
1)
Heating
Instantaneous
maximum current
(A)
205
External dimension
(mm)
Height 1,700 x Width 990 x Depth 750
Total weight
(kg)
270
260
255
Color
Silky shade (Munsell 1Y8.5/0.5)
Type
Hermetic type
Compressor
Motor output
(kW)
7.5
6.0
Fan
Propeller fan
Motor output
(kW)
0.35
Fan unit
Air volume
(m³/h)
10,000
Heat exchanger
Finned tube
Refrigerant R407C Charged amount (
*
3)
(kg)
17.0
9.0
7.0
Inverter driving side
(MPa)
OFF : 3.2
ON : 2.55
—
—
—
—
High-pressure
switch
Fixed-speed side
(MPa)
OFF : 2.55, ON : 3.2
Protective devices
(
*
5)
(
*
6)
Case heater
(W)
—
74
Gas side
(mm)
Ø28.6
Ø25.4
Liquid side
(mm)
Ø12.7
Connecting
port dia.
Balance side
(mm)
Ø9.5
Gas side
Brazing
Liquid side
Flare
Connecting
method
Balance side
Flare
Max. equivalent length
(m)
125
Max. real length
(m)
100 (However, if equivalent bend length is longer, equivalent length is the standard.)
Max. total pipe length
(Real length)
(m)
250
Outdoor unit is higher than indoor unit : 50
Refrigerant
pipe spec.
(
*
4)
Max. height difference
(m)
Outdoor unit is lower than indoor unit : 30
Control wiring
Shield wire 1.25mm² x 2 cores. up to 500m
Central remote controller
When connecting to outdoor unit : MVVS (Shield wire) 1.25mm² x 2 cores up to 500m, and
MVVS (Shield wire) 2.0mm² x 2 cores up to 1000m
Max. No. of connected indoor units
40
Sound level
(dB)
64
60Hz
*
1 : Rated conditions
Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping measns that main pipe length is 3 m, branching pipe length 2 m of branch piping connected with a 0 meter height.
*
2 : The source voltage must not fluctuate more than ±10%.
*
3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.
*
4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.
System safety protection
*
5 : Discharge temp. sensor, Suction temp. sensor, Inner overload relay, Compressor over-current relay, Over-current sensor,
Low pressure sensor.
*
6 : Discharge temp. sensor, Suction temp. sensor, Inner overload relay, Compressor over-current relay, Low pressure sensor.